![Bailey infi 90 Modular Power System II Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/bailey/infi-90-modular-power-system-ii/infi-90-modular-power-system-ii_instruction_3468074042.webp)
IMMFC05 MULTI-FUNCTION CONTROLLER
INTRODUCTION
C - 2
I-E96-427B
®
Table C-2. IMMFC05 Dipswitch SW4 Option Settings
Position
Setting
Function
1
0
Normal operation.
1
Enable special operations (refer to Table C-3).
2
0
Disable on-line configuration.
1
Enable on-line configuration.
3
0
Not used.
4
0
Perform ROM checksum routine.
1
Inhibit ROM checksum routine.
5
0
Perform ROM check.
1
Inhibit ROM check.
6
0
Normal operation.
1
Compact configuration - moves configured blocks to the top of NVRAM while moving
free space to the bottom (this is known as compacting). Leave switch OPEN and
insert module into MMU. When front panel LEDs 1,, 2 and 4 are ON,, remove the
module,, put the switch in the CLOSED position and insert the module. The MFC
goes into the configure mode and compacts the configuration.
7
0
Normal operation.
1
Initialize NVRAM (erase configuration) - leave switch OPEN and insert the module
into the MMU. When front panel LEDs 1,, 2 and 4 are ON,, remove the module,, put
the switch in the CLOSED position and insert the module. The module is now ready
to be configured. This switch must be CLOSED for normal operation.
8
0
Primary MFC module.
1
Redundant MFC module.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table C-3. IMMFC05 Dipswitch SW4 Special Operations Settings
Special
Operation
Dipswitch Position
1 2 3 4 5 6 7 8
Description
0
0 0 0 0 0 0 0 0
Force module to configure mode.
1,
1 0 0 0 0 0 0 1
Reserved for future use. If you use this setting,, your
module may not operate properly.
2
1 0 0 0 0 0 1 0
Initialize NVRAM configuration space.
3
1 0 0 0 0 0 1 1
Reserved. Do not use. If you use this setting, your mod-
ule may not operate properly.
4
1 0 0 0 0 1 0 0
INFI-NET protocol enable. This allows the MFC module
to take advantage of INFI-NET/Superloop capabilities.
5
1 1 0 1 0 0 0 0
Permit segment modification (allows change to segment
scheme configured with function code 82, specification
S1).
6
1 0 1 1 0 0 0 0
Enable time-stamping. This operation instructs the MFC
to generate time information with point data. It is applica-
ble only to INFI-NET/Superloop systems.
NOTE: 0 = CLOSED or ON,, 1 = OPEN or OFF.