Process Control andAutomation Solutionsfrom Elsag Bailey Group
E96-427
Multi-Function Controller Termination Unit
(NTMF01)
Страница 1: ...Process Control and Automation Solutions from Elsag Bailey Group E96 427 Multi Function Controller Termination Unit NTMF01...
Страница 2: ...UIPEMENTS LECTRONIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FR QUENCE RADIO DES PR CAUTIONS DEVRONT TRE PRISES LORS DE L UTILISATION DU MAT RIEL DE COMMUNICATION PORTATIF LA PRUDENCE EXIGE QUE LES PR...
Страница 3: ...Plant Loop to computer transfer module The NTMF01 Multi Func tion Controller Termination Unit provides a termination point for two separate RS 232 C ports plus a serial link to connect a control stati...
Страница 4: ...Original C 1 through C 2 Original D 1 through D 3 Original E 1 through E 3 Original F 1 through F 3 Original Index 1 through Index 2 Original When an update is received insert the latest changed page...
Страница 5: ...s avoided when servicing Special Handling This module uses Electrostatic Sensitive Devices ESD SPECIFIC CAUTIONS We strongly recommend that you turn cabinet power off before doing any termination unit...
Страница 6: ...ule contient des composantes sensibles aux decharges slectro statiques ATTENTIONS D ORDRE SP CIFIQUE Il est fortement recommande de debrancher l alimentation elec trique du cabinet avant d effectuer t...
Страница 7: ...ential Events Recorder 2 4 INSTALLING THE TERMINATION UNIT 2 5 Installing the Fuse 2 5 Mounting the Termination Unit 2 6 CABLE INSTALLATION 2 6 Termination Unit Cables 2 6 RS 232 C Communication Cable...
Страница 8: ...A 3 IMMFC03 Dipswitch U73 Baud Rate Settings A 3 A 4 Example IMMFC03 Dipswitch U75 Module Address Settings A 3 B 1 IMMFC04 Dipswitch SW3 Module Address Settings B 1 B 2 IMMFC04 Dipswitch SW4 Options S...
Страница 9: ...TE Requires Modem or Other DCE 2 8 2 7 Dipshunt Configuration for Direct Connection of Local PPT Module Acting as DTE 2 9 2 8 Dipshunt Configuration for Direct Connection of Remote PPT Module Acting a...
Страница 10: ...redundant IMMFC03 modules it enables the IMMFC03 module to com municate to a computer terminal printer or sequential events recorder through the serial ports see Figure 1 1 It also pro vides a serial...
Страница 11: ...xam ple Plant Loop to computer interface application The two mod ules use the TMF termination unit to terminate the connection of a mainframe computer terminal or modem to the INFI NET or Plant Loop c...
Страница 12: ...t mounts on the NFTP01 Field Termination Panel inside an INFI 90 cabinet The board con tains Two DB 25 connectors Relays Connector sockets Dipshunts Fuse Light emitting diodes LED Faston connectors fo...
Страница 13: ...other services available from Bailey Controls Company Appendices Briefly discuss the modules that use the termination unit and provide a cross reference of dipswitch and jumper settings for those modu...
Страница 14: ...odules Table 1 1 Glossary of Terms and Abbreviations continued Term Definition Table 1 2 Reference Documents Number Description I E93 902 1 NDCS03 Digital Control Station I E96 117 IISAC01 Analog Cont...
Страница 15: ...station serial link Cable Insulation Specifications PVC UL Rating CL2 Non PVC UL Rating PLTC 80 C 176 F at 300 V 90 C 194 F at 300 V Mounting Screw mounts on the field termination panel Environmental...
Страница 16: ...g Bag Keep the modules in the static shielding bag until you are ready to install them in the system Save the bag for future use 2 Ground Bag Before Opening Before opening a bag con taining an assembl...
Страница 17: ...tive handshake lines Each port can be configured as a DTE or DCE device Only port two can terminate a diagnostic terminal The termi nation unit can interface with Devices Printer Sequence of events re...
Страница 18: ...nframe Computer The INICT01 and INPCT01 modules can interface to a main frame computer MODCOMP or VAXstation To set up the termination unit to terminate a mainframe see Figure 2 5 and install the appr...
Страница 19: ...2 Dipshunt Configuration for Direct Connection to Host Computer IMMFC03 and ICT Modules P1 CONNECTOR STATION COMMUNICATION P2 CONNECTOR TERMINAL PORT 1 PRINTER PORT 2 PORT 2 PORT 1 F1 FUSE 24 V E2 I O...
Страница 20: ...OR STATION COMMUNICATION P2 CONNECTOR TERMINAL PORT 1 PRINTER PORT 2 PORT 2 F1 FUSE 24 V E2 I O COMMON E3 COMMUNICATION THROUGH A MODEM TMF ACTING AS DTE T00382A P3 CONNECTOR ICT MUST USE P1 CONNECTOR...
Страница 21: ...TION After mounting the termination unit to the field termination panel install the termination cables Termination Unit Cables Table 2 1 lists the cables their application connector assign ments and m...
Страница 22: ...nd of the appropriate cable in the module mounting unit MMU backplane slot assigned to the module Figure 2 5 Dipshunt Configuration for Direct Connection to Mainframe Computer ICT Module P1 CONNECTOR...
Страница 23: ...232 C cable 1 Turn off power to host computer or terminal Figure 2 6 Dipshunt Configuration for PPT Module Acting as DTE Requires Modem or Other DCE P1 CONNECTOR STATION COMMUNICATION P2 CONNECTOR TE...
Страница 24: ...am in Fig Figure 2 7 Dipshunt Configuration for Direct Connection of Local PPT Module Acting as DTE V 9 6 V 9 20 5 2 5 4 3 12 SRD 16 5 3 4 8 BUSY 25 6 20 1 2 DCD CTS CTS CTS 4 TO 5 RXD RTS CTS TXD J2...
Страница 25: ...tion of Remote PPT Module Acting as DCE P1 CONNECTOR STATION COMMUNICATION P2 CONNECTOR TERMINAL PORT 1 PRINTER PORT 2 PORT 1 PORT 2 F1 FUSE 24 V E2 I O COMMON E3 T00428B P3 CONNECTOR XU1 XU2 J1 J2 XU...
Страница 26: ...C RXD DCD TXD CTS DSR RTS 9 4 1 GND 3 8 2 5 6 DCD CTS CTS CTS CTS 4 TO 5 RXD RTS CTS TXD J2 11 STD 14 CTS RXD RTS DCD RI 22 CTS RTS GND TXD V 9 6 V 9 20 5 2 5 4 3 12 SRD 16 5 3 4 8 BUSY 25 6 20 1 2 FU...
Страница 27: ...PRINTER PORT 2 PORT 2 ONLY FOR DIAGNOSTIC TERMINAL F1 FUSE 24 V E2 I O COMMON E3 T00745A P3 CONNECTOR XU1 XU2 J1 J2 XU4 XU4 XU3 XU3 24 VDC DSR DCD RXD CTS TXD 9 6 8 3 5 2 DCD CTS CTS CTS 4 TO 5 RXD R...
Страница 28: ...ndant module NOTE 1 The specified maximum length only applies to the HCBL01 cable The performance of INFI 90 modules does not place a restriction on the maximum length of the RS 232 C cable Follow ind...
Страница 29: ...s de raccordement du chassis Des dommages aux equipements pourraient survenir dans le cas contraire Ne pas rebrancher l alimentation avant que toutes les connexions aient ete verifiees RXD RECEIVE DAT...
Страница 30: ...a 14 AWG wire from the I O common bus bar at the bottom of the cabinet to the E3 faston of the termination unit The NTMF01 termination unit is ready for operation if 1 The fuse is installed 2 The dips...
Страница 31: ...s a mainte nance schedule MAINTENANCE SCHEDULE Execute the tasks in Table 3 1 at the specified intervals Table 3 1 Maintenance Schedule Task Interval Clean and tighten all power and field wiring conne...
Страница 32: ...ermination unit is faulty replace it with a new one Do not try to repair the unit replacing compo nents may affect the unit performance and certification When replacing a termination unit observe the...
Страница 33: ...heir connector assignments as you remove them 6 When all the cables are removed from the termination unit remove the 2 mounting screws and the chassis ground screw with star washer at E1 and remove th...
Страница 34: ...ert it into its module mounting unit slot The module should be seated in the termination unit cable at the rear of the MMU card cage when fully inserted 15 After all the cables have been replaced retu...
Страница 35: ...t number and quantity 2 Model and serial numbers if applicable 3 Bailey instruction manual number page number and refer ence figure that identifies the part Order parts without commercial descriptions...
Страница 36: ...U board For more information on the module refer to the IMMFC03 Multi Function Controller Module product instruction Figure A 1 IMMFC03 Module CPU Board Layout Table A 1 IMMFC03 Dipswitch U72 Option S...
Страница 37: ...le NOTE 0 CLOSED or ON 1 OPEN or OFF Table A 2 IMMFC03 Dipswitch U72 Special Operation Settings Special Operation Dipswitch Position 1 2 3 4 5 6 7 8 Description 0 0 0 0 0 0 0 0 0 Force module to confi...
Страница 38: ...1 0 0 1 1 0 0 1 110 0 0 1 0 0 0 1 0 0 2400 0 0 1 0 1 0 1 0 1 134 5 1 1 0 0 1 1 0 0 3600 0 1 1 0 1 1 1 0 1 150 0 0 0 1 0 0 0 1 0 4800 0 0 0 1 1 0 0 1 1 300 0 1 0 1 0 1 0 1 0 7200 0 1 0 1 1 1 0 1 1 600...
Страница 39: ...are reserved for future use The positions of J23 and J24 do not affect module operation Figure B 1 IMMFC04 Module Layout T00022B P1 P2 P3 STATUS LED GROUP LEDS XU39 XU40 SW4 OPTIONS SW3 MODULE ADDRES...
Страница 40: ...ove the module put the switch in the CLOSED position and insert the module The module is now ready to be configured This switch must be CLOSED for normal operation 8 0 Primary MFC module 1 Redundant M...
Страница 41: ...hould not be changed Jumpers J23 and J24 are reserved for future use The positions of J23 and J24 do not affect module operation Figure C 1 IMMFC05 Module Layout T00024A P1 P2 P3 STATUS LED GROUP LEDS...
Страница 42: ...ve the module put the switch in the CLOSED position and insert the module The module is now ready to be configured This switch must be CLOSED for normal operation 8 0 Primary MFC module 1 Redundant MF...
Страница 43: ...settings for the CPU board For more information on the module refer to the INPPR01 Plant Loop to Plant Loop Remote Interface prod uct instruction NOTE Jumpers J1 through J3 are factory set Do not cha...
Страница 44: ...and port and port 2 as its reply port 3 The remote INPPR01 interface uses port 2 as its command port and port1 as its reply port 4 Both the local and remote interface must have a loop address of 0 U75...
Страница 45: ...R MODULE INTRODUCTION I E96 427B D 3 Table D 3 Example INPPT01 Dipswitch U75 Loop Address Settings Address Example Dipswitch Position Binary Value 1 16 2 8 3 4 4 2 5 1 7 0 0 1 1 1 15 0 1 1 1 1 31 1 1...
Страница 46: ...formation on the module refer to the INPCI02 Plant Loop to Computer Interface product instruc tion NOTE Jumpers J1 through J3 are factory set Do not change the jumper settings Figure E 1 INPCT01 Modul...
Страница 47: ...d the PCT module will expect all commands from the host to include a checksum byte as the last charac ter before the carriage return The PCT module includes a checksum in each reply 8 N A This dipswit...
Страница 48: ...MODULE INTRODUCTION I E96 427B E 3 Table E 3 Example INPCT01 Dipswitch U75 Loop Address Settings Address Example Dipswitch Position Binary Value 1 16 2 8 3 4 4 2 5 1 7 0 0 1 1 1 15 0 1 1 1 1 31 1 1 1...
Страница 49: ...on on the module refer to the INFI NET Communication Modules product instruction NOTE Jumpers J1 through J3 are factory set Do not change the jumper settings Figure F 1 INPCT01 Module CPU Board Layout...
Страница 50: ...ption is enabled the ICT module will expect all commands from the host to include a checksum byte as the last charac ter before the carriage return The ICT module includes a checksum in each reply 8 N...
Страница 51: ...75 Diagnostic Settings Position Setting Function 1 0 NIS handshake time out enabled 1 NIS handshake time out disabled 2 0 NIS diagnostic disabled 1 NIS diagnostic enabled 3 0 INFI NET diagnostic utili...
Страница 52: ...ol SER 740 2 11 INPPT01 2 3 Mainframe computer 2 3 PPT module acting as DTE 2 8 Rochester 3800 2 11 Rochester ISM 2 12 Dipshunt locations 2 3 Dipswitch settings IMMFC03 U72 A 1 U73 A 3 U75 A 3 IMMFC04...
Страница 53: ...IMMFC05 C 1 N Nomenclature 1 5 O Overview 1 1 R Recommended spare parts list 4 1 Reference documents 1 5 Repair 4 1 Replacement 4 1 Fuse 4 1 Parts and ordering information 5 1 Termination unit 4 1 RS...
Страница 54: ...8756 ASIA PACIFIC 152 Beach Road Gateway East 20 04 Singapore 189721 Telephone 65 391 0800 Telefax 65 292 9011 EUROPE AFRICA MIDDLE EAST Via Puccini 2 16154 Genoa Italy Telephone 39 10 6582 943 Telefa...