INTRODUCTION
I-E96-613A
D - 1
APPENDIX D - NIMP01/NIMP02 TERMINATION MODULE
CONFIGURATION
INTRODUCTION
The INIPT02 INFI-NET to Plant Loop Transfer Module (through
the IMMPI01 Multi-Function Processor Interface Module) can
use the NIMP01 and NIMP02 termination module for termina-
tion. Jumpers on the NIMP01 module configure the two
RS-232-C ports for data terminal equipment (DTE) or data
communication equipment (DCE). One of the RS-232-C ports
can be configured as an RS-485 port. The NIMP02 module is
required when installing redundant IPT modules. Refer to the
NIMP01 and NIMP02 instruction for complete information on
termination module applications.
Figures
through
show the jumper configurations for
jumpers J1 and J2. Figure
shows the jumper configura-
tions for jumpers J5 through J10. Figure
shows the
jumper configurations for jumpers J14 through J17.
Figure
shows the NIMP01 connector and jumper locations.
Figure
shows NIMP01 cable connections. Refer to
for cable diagrams and information on how to
install redundant termination modules.
Jumpers J11 and J12 are storage posts for extra jumpers.
Jumper J13 is normally set with pins one and two connected.
Jumper J18 configures the terminal serial port for RS-485
operation when pins two and three are connected and connec-
tor P7 is used instead of connector P5.
NOTES:
1.
RS-232-C port connections on the IMP module are through
DB-9 connectors. Use Bailey Controls cable NKMR02 to connect a
standard piece of equipment (computer or printer with a DB-25 con-
nector) to the IMP module.
2.
There are no jumper settings on the NIMP02 termination module.