INSTALLATION
INNIS01 MODULE INSTALLATION
I-E96-613A
3 - 9
INNIS01 MODULE INSTALLATION
If the NIS dipswitches and jumpers are properly configured, it
is ready to be installed in the module mounting unit.
Figure
shows example installations of the NIS module. To
install the NIS module:
1. Verify the NIS slot assignment in the module mounting
unit.
2. Verify that a 24-pin dipshunt is installed in the I/O
expander bus sockets between the module mounting unit slot
to be used by the NIS module and the slot to be used by the IPT
module.
NOTE: When installing the INNIS01, IMMPI01 and INIPT02 mod-
ules, there must be continuity between the INNIS01 and INIPT02
modules.
3. Remove any 24-pin dipshunts from the I/O expander bus
sockets that would connect the NIS module to any module
other than the INIPT02 or IMMPI01 module and any required
I/O modules.
4. Attach the hooded end of the NKLS01, NKLS02, NKLS11 or
NKLS12 cable to the module mounting unit backplane cable
connector opening for the NIS module.
5. Slide the NIS module in while guiding the top and bottom
edges of the circuit board along the top and bottom rails of the
module mounting unit.
6. Push on the faceplate until the rear edge of the module is
firmly seated in the backplane connector.
7. Turn the 2 latching screws
1
/
2
-turn to lock the module in
place. The module is locked into place when the open side of
the slot on the latching screws faces the center of the faceplate.
WARNING
Disconnect power before installing dipshunts on the module
mounting unit backplane. Failure to do so will result in contact
with cabinet areas that could cause severe or fatal shock.
AVERTISSEMENT
Interrompez l'alimentation avant d'installer des dipshunts sur
le fond de panier du châssis de montage des modules. Sinon,
tout contact avec cette zone entraîne des risques d'électrocu-
tion sérieuse ou fatale.