INSTALLATION
INIPT02 AND IMMPI01 MODULE INSTALLATION
I-E96-613A
3 - 17
INIPT02 AND IMMPI01 MODULE INSTALLATION
If the INIPT02 and IMMPI01 dipswitches and jumpers are prop-
erly configured, the modules are ready to be installed in the
module mounting unit.
To determine if the NMMU0
module mounting unit uses
-30 VDC:
1. Locate the -30 VDC faston. It is the second faston from the
top when viewing the module mounting unit from the rear.
2. Check for -30 VDC with respect to system common at the
-30 VDC faston.
3. If -30 VDC is present, set the jumper J5 of the IPT module
to the appropriate positions.
To install the IPT and MPI modules (see Figure
1. Verify the IPT and MPI slot assignments (IPT module in the
right slot, MPI module in the left slot) in the module mounting
unit are adjacent to its associated NIS module.
Figure 3-8. IMMPI01 Jumper J2 Settings
RTSB (+)
RTSB (-)
TP25209A
1
3
5
2
4
6
7
8
FOR RTSB
HANDSHAKE
DUART
DUART
P3-29
P3-14
DUART
DUART
RTSB/DIGOUT 2 (+)
DIGOUT 2 (+)
RTSB/DIGOUT 2 (-)
DIGOUT 2 (-)
CAUTION
To avoid potential module damage, evaluate your system for
compatibility prior to module installation. The INIPT02 module
uses connections to the module mounting unit backplane that
served other functions in early Network 90 systems.
ATTENTION
Afin d'éviter tout dommage au module, évaluer la compatibilité
avec votre système avant l'installation du module. Le module
INIPT02 utilise des connexions sur le panneau arrière du chas-
sis de montage des modules qui servaient à d'autres fonctions
dans les systèmes Network 90 de premières générations.