INSTALLATION
INIPT02 INFI-NET TO PLANT LOOP TRANSFER MODULE CONFIGURATION
I-E96-613A
3 - 11
INIPT02 INFI-NET TO PLANT LOOP TRANSFER MODULE CONFIGURATION
The INIPR01 INFI-NET to Plant Loop Remote Interface (IPR)
includes an INIPT02 INFI-NET to Plant Loop Transfer Module
(IPT). Configure the IPT module as follows.
NOTES:
1.
Two IPR interfaces are required for a complete INFI-NET to
Plant Loop connection.
2.
The INIPT02 module uses connections to the module mounting
unit backplane that served other functions in early Network 90 sys-
tems. To avoid potential module damage, evaluate your system for
compatibility prior to module installation. Early Network 90 systems
applied -30 VDC to pins three and four of the module connector P1.
This voltage is not required for INFI 90 modules. In INFI 90 systems,
pin four is used for the Controlway bus. If your system contains
modules that require -30 VDC, set jumper J5 to the 30 VDC position.
Doing so allows the installation of the IPT module in a module
mounting unit that uses -30 VDC and limits communication to the
module bus.
Dipswitch Settings
The IPT module consists of one circuit board. The board has
four dipswitches. These dipswitches select module operation
options, and serial port communication characteristics and
baud rate. Figure
shows the dipswitch locations. Module
placement within the module mounting unit is important when
installing an IPT module with the MPI module. Installing an
MPI module with the IPT module requires two adjacent slots in
a module mounting unit. The IPT module must occupy the
right slot (when facing the front of the module mounting unit)
and the MPI module must occupy the left slot.
Figure 3-5. INIPT02 Dipswitch and Jumper Locations
CR17
J4
J1
P5
P4
SW6
SW4
1 2 3 4 5
OPEN
6 7 8
SW1
1 2 3 4 5
OPEN
6 7 8
SW2
1 2 3 4 5
OPEN
6 7 8
SW3
1 2 3 4 5
OPEN
6 7 8
HW SETUP
J2
J5
P2
P3
P1
2MBIT
30V
MODB
1MBIT
4MBIT
1
16
2
15
3
14
4
13
5
12
6
11
7
10
8
9
TP21180A