OPERATING PROCEDURES
INIPR01 MODES OF OPERATION
4 - 4
I-E96-613A
®
Stop/Reset Pushbutton
Push the stop/reset pushbutton once and wait for the status
LED to turn red before removing an IPT module from the mod-
ule mounting unit. Pressing the stop/reset pushbutton again
causes the restoration of the IPT module to power up values
after a halt. It is also used to recover from an operator initiated
stop or a module time-out.
INIPR01 MODES OF OPERATION
The INIPR01 INFI-NET to Plant Loop Remote Interfaces have
two modes of operation: Execute and configure.
Execute Mode
This is the normal mode of operation for the IPR interface. In
the execute mode, the IPT module on the INFI-NET system
communicates with the IPT module on the Plant Loop system.
The IPT module (while in execute mode) can process exception
reports, allow the operator to adjust tunable module specifica-
tions, and configure modules within a node residing on the
INFI-NET system.
Configure Mode
The configure mode allows the executive block configuration to
be modified. While in configure mode, all IPT module functions
continue to operate normally. Any changes made to the execu-
tive block (function code 203) of the IPT module have no effect
until the module returns to execute mode. Use an INFI 90
operator interface device to do any configuration tasks. Refer to
the product instruction for the operator interface used for
details.
INIPT02 MODULE EXECUTIVE BLOCK CONFIGURATION
To change the IPT executive block specifications, the module
must be in the configure mode. New (changed) specification
values will not become effective until the module is reset or the
module is placed in execute mode. Changing the mode to exe-
cute will cause the module to do a software reset.
Use CAD/TXT release 5.3 or later to configure the INIPT02
executive block (function code 203). A configuration tuning
module (CTM) can be used to configure the executive block of
the IPT module. To use a CTM module, set the IPT module to
module bus communication and set the CTM module to
address the IPT module. A configuration tuning terminal (CTT)
along with an IMCPM01 or IMCPM02 Communication Port
Module can also be used to configure the executive block of the
IPT module.