TROUBLESHOOTING
INIPT02 ERROR CODES
5 - 2
I-E96-613A
®
INIPT02 ERROR CODES
If module errors occur while the IPT module is operating, the
module halts operation and the status LED turns red and the
CPU LEDs on the module faceplate display error codes.
Table
lists the IPT error codes and associated corrective
action. Nonfatal module errors appear in the module status
report from the operator interface.
Table 5-2. INIPT02 Error Codes
Code
LED
8
7
6
5
4
3
2
1
Condition
Corrective Action
01
0
0
0
0
0
0
0
1
NVRAM error. NVRAM not ini-
tialized or bad checksum.
Initialize NVRAM.
02
0
0
0
0
0
0
1
0
NVRAM write error
Initialize NVRAM.
0B
0
0
0
0
1
0
1
1
NVRAM initialized
Set dipswitch SW4 pole 5 to 0 and
reset the module.
0D
0
0
0
0
1
1
0
1
Intermodule link error
Check cable between primary and
secondary IPT modules. Check
cable between IPT and termination
device.
0E
0
0
0
0
1
1
1
0
Redundancy switches
Verify pole 8 of dipswitch SW4 is
set properly. Set pole 7 of
dipswitch SW4 to 1.
12
0
0
0
1
0
0
1
0
NIS not responding
Check dipshunt between NIS and
IPT. Replace NIS.
13
0
0
0
1
0
0
1
1
ROM checksum error
Replace NIS.
14
0
0
0
1
0
1
0
0
I/O expander bus message
failure
Reset IPT. Replace if error recurs.
15
0
0
0
1
0
1
0
1
Loop failure
Correct loop integrity problem.
16
0
0
0
1
0
1
1
0
NIS loopback test failure
Check cabling between NIS and
loop termination device.
17
0
0
0
1
0
1
1
1
Power system status failure
Check power system. Call Bailey
field service if error recurs.
21
thru
2F
0
0
1
0
0
0
0
1
0
0
1
0
1
1
1
1
Software error
Call Bailey field service.
31
0
0
1
1
0
0
0
1
Memory or CPU fault
Replace IPT.
32
0
0
1
1
0
0
1
0
Address or bus error
Reset IPT, replace IPT if error con-
tinues.
33
0
0
1
1
0
0
1
1
Illegal instruction
34
0
0
1
1
0
1
0
0
Trace/privilege violation
35
0
0
1
1
0
1
0
1
Spurious/unassigned excep-
tion
36
0
0
1
1
0
1
1
0
Divide by 0/checksum/format
error
37
0
0
1
1
0
1
1
1
Any trap instruction
38
0
0
1
1
1
0
0
0
Invalid NIS dipswitch setting
Configure the NIS dipswitches cor-
rectly.