INSTALLATION
INIPT02 AND IMMPI01 MODULE INSTALLATION
3 - 18
I-E96-613A
®
2. Push one end of the 60-pin ribbon cable through the cable
slot and connect it to connector P5 on the IPT module (see Fig-
ure
).
3. Connect the other end of the cable to connector P6 on the
MPI module (see Figure
4. Verify that a 24-pin dipshunt is installed in the I/O
expander bus sockets between the module mounting unit slot
to be used by the NIS module and the slots to be used by the
IPT and MPI modules.
NOTES: When installing the NIS, MPI and IPT modules, there must
be continuity between the NIS and IPT modules. Observe the
following:
1.
Install one dipshunt in the I/O expander bus socket between the
NIS slot and IPT slot if the NIS module is mounted to the right of the
MPI/IPT combination.
2.
If the NIS module is mounted to the left of the IPT module, two
dipshunts are required. Install one dipshunt between the NIS slot
and MPI slot. Install the second dipshunt between the MPI slot and
the IPT slot.
5. Remove any 24-pin dipshunts from the I/O expander bus
sockets that would connect the IPT or MPI modules to any
module other than those making up the IPR interface and any
required I/O modules.
6. Attach the hooded end of the NKTU01, NKTU02, NKTU11
or NKTU12 cable to the module mounting unit backplane cable
connector opening for the IPT module. The other end of the
cable attaches to the termination device or to the termination
mounting unit backplane.
7. Slide the IPT and MPI modules in while guiding the top and
bottom edges of the circuit boards along the top and bottom
rails of the module mounting unit.
8. Push on the faceplate until the rear edges of the modules
are firmly seated in the backplane connectors.
WARNING
Disconnect power before installing dipshunts on the module
mounting unit backplane. Failure to do so will result in contact
with cabinet areas that could cause severe or fatal shock.
AVERTISSEMENT
Interrompez l'alimentation avant d'installer des dipshunts sur
le fond de panier du châssis de montage des modules. Sinon,
tout contact avec cette zone entraîne des risques d'électrocu-
tion sérieuse ou fatale.