INTRODUCTION
SPECIFICATIONS (continued)
1 - 6
I-E96-309A
®
SPECIFICATIONS
(continued)
Outputs
24 V Logic
Low Level Output Voltage
24 V Logic
High Level Output Current
24 V maximum
Sink Current
10 V typical (sink current = 120 mA)
2.0 V maximum
100
µ
A maximum
120 mA
Propagation Delay Times
Input
Output
Low to high 50
µ
sec. typical
High to low 25
µ
sec. typical
Low to high 25
µ
sec. typical
High to low 100
µ
sec. typical
Isolation Voltage
150 V RMS Channel to channel
150 V RMS Channel to logic
Surge Withstand
Meets requirements of IEEE Capability
Standard 472-1974, on input and output channels.
Maximum Wire Sizes
12 AWG from field wiring to NTDI01
Environmental Specifications
Ambient Temperature
Relative Humidity
Atmospheric Pressure
Air Quality
0
o
to 70
o
C (32
o
to 158
o
F)
0% to 95% up to 55
o
C (131
o
F) (non-condensing)
0% to 45% at 70
o
C (158
o
F) (non-condensing)
Sea level to 3 km. (1.86 miles)
Noncorrosive
Mounting
Uses 1 slot in Infi 90 Module Mounting Unit.
Certification
CSA certified for use as process control equipment
in an ordinary (non-hazardous) location.