INSTALLATION
SETUP
I-E96-309A
3 - 5
Module Configuration Switch
The module configuration switch shown in Figure
contains
four contacts. These contacts:
•
Allow the DSM to interface with a master and field devices.
•
Allow the DSM to interface with a Digital Logic Station.
•
Set the operation (input or output) of each point group
within the I/O circuitry.
•
Set the operation of each point group during default.
Contact 3 of the module configuration switch determines the
unit to which the module interfaces. If the module is an I/O
interface between a master and field devices (such as
pushbuttons or relays), then the contact must be in the 0 or
closed position. If the module is to interface between a master
Figure 3-3. Module Configuration Switch
ENABLE
SWITCH
ADDRESS
SELECTION
SWITCH
MASTER
SELECTION
JUMPERS
I/O
JUMPERS
(J1-J16)
DEFAULT VALUE
SWITCHES
TP35703A
1
1
2
OPEN
OPEN
8
1
OPEN
8
1
OPEN
8
1
OPEN
4
J17
J18
J3
J1
J4
J2
J7
J8
J5
J6
J10
J13
J14
J9
3
1
2
3
1
2
3
1
2
3
2
1
J11
3
2
1
J12
3
2
1
J15
3
2
1
J16
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
1
1
2
2
3
3
MODULE CONFIGURATION SWITCH
1
OPEN
2
3
4
0
I/O WITH FIELD DEVICES
ALL OUTPUTS DRIVEN TO DEFAULT
VALUE ON MASTER FAILURE
ALL OUTPUTS HOLD ON MASTER FAILURE
DLS (CONTACTS 1 AND 2 MUST BE SET FOR
OUTPUTS AND CONTACT 4 SET CLOSED)
GROUP B INPUTS
GROUP A INPUTS
GROUP A OUTPUTS
GROUP B OUTPUTS