INSTALLATION
SETUP
3 - 2
I-E96-309A
®
SETUP
Prior to installation, set the address of the DSM and install
jumpers to configure the digital outputs and inputs. Be sure
you configure the termination unit (TU) or termination module
(TM) to accept the field device signals. Figure
shows the 5
switches and 18 jumpers to set on the DSM. The module
switches and jumpers are:
•
An address switch and an enable switch determine the
address bytes that precede every data transfer (one module
address byte for the MFP/LMM).
•
A module configuration switch sets the output to the exist-
ing or default value during a communication break with the
master.
•
Two default value switches set the default value of the A
group and B group outputs.
•
Two master selection jumpers select a LMM or MFP master
for the DSM.
•
Sixteen two-position jumpers set outputs for two-wire iso-
lated or normal output operation.
Figure 3-1. Switches and Jumpers
ENABLE
SWITCH
ADDRESS
SELECTION
SWITCH
MODULE CONFIGURATION
SWITCH
I/O
JUMPERS
(J1-J16)
MASTER
SELECTION
JUMPERS
DEFAULT VALUE
SWITCHES
TP35704A
1
1
2
OPEN
OPEN
8
1
OPEN
8
1
OPEN
8
1
OPEN
4
J17
J18
J3
A3
A1
J1
J4
J2
J7
J8
A4
A2
A7
A8
A5
A6
B2
B5
B6
B1
J5
J6
J10
J13
J14
J9
3
1
2
3
1
2
3
1
2
3
2
1
J11
B3
3
2
1
J12
B4
3
2
1
J15
B7
3
2
1
J16
B8
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
1
1
2
2
3
3