TROUBLESHOOTING
NETWORK INTERFACE UNIT TEST UTILITY
4 - 6
WBPEEUI220754A0
®
NETWORK INTERFACE UNIT TEST UTILITY
An off-line NNIU01 network interface unit test allows restart-
ing the network interface unit and testing loop communica-
tions. This may be required if there is a problem bringing the
console on-line, and a network interface unit or loop problem
is suspected.
NOTES:
1.
Care should be taken when using this utility. It causes a net-
work interface unit restart. If the network interface unit is restarted
while the OIS console is on-line, normal operation is interrupted.
2.
Access the utility from the OISENGR account.
27
Time out between bytes in command.
28
Index already established by another node.
29
Point type incompatible with command.
30
Watchdog time-out.
31
Checksum compare error.
32
Destination node off-line.
33
Callup command required.
34
NIU error.
35
NIU busy.
36
NIS/BTM module off-line.
37
Conflict with monitor mode.
38
Point type incorrect.
39
Destination ring off-line.
40
Destination node busy.
41
Destination ring busy.
100
Undefined message type for target module.
101
Busy - cannot respond at this time.
102
Mode for command does not agree with current module mode.
103
Message data out of range.
104
Invalid block number.
105
Undefined block number - block is valid but not configured.
106
Block not readable - block number is valid but has no readable parameters.
107
Invalid function code for target module.
108
Function code and block number not compatible in target module.
109
Insufficient memory to write block in NVRAM and/or RAM.
110
Module not responding.
Table 4-4. NNIU01 Network
Interface Unit Error Codes
(continued)
Decimal
Error Code
Error Description