INTRODUCTION
OIS CONSOLE SPECIFICATIONS
1 - 8
WBPEEUI220754A0
®
Keyboard Interface
Alarm relays
Alarm tones
Operator keyboard output relays rated at 250 mA 24-28 VDC per IIMKM02A
module.
6 per keyboard
5 per keyboard
Keyboards
1 Mylar (operator)
1 Engineering (QWERTY)
Trackball or mouse
1
Annunciator display panels
4 (per IIMKM02A module) 32 pushbuttons and LEDs per panel
Color video copier
1 (IIPRT04)
Printers per unit
4 (Logging)
4 (Copy screen)
Data archiving media
DAT magnetic tape/optical disk
Maximum trend storage
Three months (refer to the operation instruction)
Configuration
Nonvolatile ROM and hard disk memory
Environment
Temperature
Relative humidity
Altitude
Operating: 10° to 40°C (50° to 104°F)
Storage: -20° to 60°C (-4° to 140°F)
Operating: 20% to 80% noncondensing. Recommended minimum 40%.
Storage: 10% to 90% noncondensing.
-0.3 to +2.4 km (-0.2 to 1.5 mi)
Cooling requirements
(Heat dissipation)
Dimensions
Table 1-5. OIS42 Console Specifications
(continued)
Property
Characteristic/Value
Alarm Relays
Rating
Contact Voltage
24 VDC
Contact Current
0.25 A
Contact Power
6 W
Model
BTU/Hr
Nominal
BTU/Hr
Maximum
IIOIS42X1
881
1,145
IIOIS42X2
881
1,145
IIOIS42X3
1,359
1,767
IIOIS42XA
547
710
IIOIS42XD
1,093
1,457
Model
Height
Width
Depth
cm.
in.
cm.
in.
cm.
in.
IIOIS42X1
107.27
42.23
71.12
28.00
109.01
42.92
IIOIS42X2
156.94
61.78
71.12
28.00
109.01
42.92
IIOIS42X3
156.94
61.78
71.12
28.00
109.01
42.92
IIOIS42XA
221.28
87.12
60.96
24.00
76.20
30.00
IIOIS42XD
221.28
87.12
60.96
24.00
76.20
30.00