INTRODUCTION
SPECIFICATIONS
1 - 10
WBPEEUI240755B0
®
Magnetic and electromagnetic fields
(continued)
Damped oscillatory magnetic
field, 0.1 MHz and 1 MHz
(IEC 1000-4-10, EN 61000-4-10)
Peak value: 30 A/m
Radiated radio-frequency elec-
tromagnetic field, 80 MHz to
1 GHz (ENV 50140)
Unmodulated rms: 10 V/m
Amplitude modulated: 80% AM (1 kHz)
Radiated radio-frequency field,
900 ±5 MHz (ENV 50204)
Unmodulated rms: 10 V/m
Pulse modulated: Duty cycle 50%
Rep. cycle 200 Hz
Radio-frequency common
mode, amplitude modulated,
0.15 MHz to 80 MHz
(ENV 50141)
Unmodulated rms: 10 V/m
Amplitude modulated: 80% AM (1 kHz)
Source impedance: 150
Ω
Emission test
RF radiated fields, 30 MHz to 1000
MHz (ENV 55011)
Class A
CE Mark Declaration
EMC96 Directive 89/336/EEC
Low Voltage Directive 73/23/EEC
This product, when installed in an INFI 90 OPEN cabinet, complies
with the following Directives/Standards requested for CE marking:
EN50081-2 Generic Emission Standard - Part 2: Industrial
Environment
EN50082-2 Generic Immunity Standard - Part 2: Industrial
Environment
EN 61010-1 Safety Requirement for Electrical Equipment for Mea-
surement, Control and Laboratory Use - Part 1: General
Requirements
Certifications
CSA (Canadian Standards
Association)
FM (Factory Mutual)
pending
Certified for use as process control equipment in an ordinary
(nonhazardous) location per CSA 22.2 No. 1010.1-92
Approval for the following categories.
Nonincendive for:
Class I, Division 2, Groups A,B,C,D
Class II, Division 2, Groups F,G
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
Table 1-5. Specifications
(continued)
Property