SECTION 7 - REPAIR/REPLACEMENT PROCEDURES
INTRODUCTION
This section explains the replacement procedures for an
IMCIS12 and IMQRS12 modules. There are no special tools
required to replace CIS and QRS modules.
MODULE REPAIR/REPLACEMENT PROCEDURES
If you determine the CIS or QRS module is faulty, replace it
with a new one. Do
not
try to repair the module; replacing
components may affect the module performance. You can
remove the module while system power is supplied. To replace
a module:
1. Push and turn the two front panel captive retaining screws
one half turn to unlatch the module. It is unlatched when the
slots on the screws are vertical and the open end of the slots
face away from the module.
2. Gently slide the module out of the MMU.
3. Configure the replacement module switch and jumper set-
tings. Ensure they are set the same as the original module.
4. In the same slot assignment as the original module, align
the replacement module with the guide rails in the MMU; gen-
tly slide it in until the front panel is flush with the top and bot-
tom of the MMU frame.
5. Push and turn the two captive retaining screws on the
module front panel one half turn to the latched position. It is
latched when the slots on the screws are vertical and the open
ends face the center of the module.
6. Return to normal operation.