OPERATING PROCEDURES
START-UP PROCEDURES
4 - 2
WBPEEUI240755B0
®
START-UP PROCEDURES
The multi-function processor (MFP) controls the start-up of the
CIS and QRS modules; it is fully automatic. Function Code
(FC) 79 in the MFP configuration enables the I/O module.
Specification S1 (FC 79) is the I/O module address. It must be
the same as the address set on the I/O module address switch
(S1). The front panel LED (solid green) verifies that the module
is enabled and communicating.
FUNCTION CODE CONFIGURATION
Configure the control module so that the CIS or QRS module
will operate within the system control strategy. To configure
the control module, the following instruction manuals are nec-
essary.
•
Instruction manual for the operator interface/configuration
device in the system (i.e., OIS, CTM, EWS).
•
Function Code Application Manual.
•
Instruction manual for the control module in the system.
Refer to Table
for a listing of applicable instruction manuals.