19
5. Settings
Settings
The necessary basic settings required for the
control function are made in the menu “5. Set
-
tings”.
Caution
This does not under any cir-
cumstances replace the safety
facilities to be provided by the
customer!
The menu is closed by pressing the “esc” key
or selecting “Exit settings”.
Various settings can be made depending on the selection of hydraulic
variant (see “7.1. Program selection” on page 23).
Caution
5.1. Tmin S1
Enable/start temperature at sensor 1
If this value is exceeded at sensor 1 and the other conditions are also met, the con
-
troller switches the associated pump and/or ball value on. If the temperature at sensor
1 drops below this value by 5 °C, the pump and/or the valve are switched off again.
Setting range: 0 °C - 99 °C/Default: 20 °C
5.2. Tmax S2
Switch-off temperature at sensor 2
If this value is exceeded at sensor 2, the controller switches the associated pump and/
or valve off. If sensor 2 falls below this value again and the other conditions are also
met, the controller switches the pump and/or ball value on again.
Setting range: 0 °C - 99 °C/Default: 30 °C
Danger
Temperature values which are set too high can lead to scalding or dam-
age to the system. Scalding protection must be provided by the cus-
tomer!