The instrument may also enter several special states, these are indicated by the specific analog
output levels indicated below:
Mode of Operation
1-5V
0-5V
2-10V
0-10V
4-20mA
Instrument Fault
≤ 0.3V
N/A
≤ 0.6V
N/A
≤ 1.2 mA
Offline Mode / Maintenance
0.75V
N/A
1.5V
N/A
3 mA
Drift Below Zero
0.95V
N/A
1.9V
N/A
3.8 mA
Normal Operation
1-5V
0-5V
2-10V
0-10V
4-20 mA
Measuring Range Exceeded
5.12V
5.12V
10.25V
10.25V
20.5 mA
Fault on Analog Interface
> 5.25V
> 5.25V
> 10.5V
> 10.5V
> 21mA
4.1.3 Verifying the Modbus Signal
The MGS-400 gas detectors provide a Modbus RTU digital interface. All status messages and
most parameters can be accessed and / or configured via the MGS-400 App
(Bluetooth
®
communications)
or via a Building Management
(Modbus network)
.