1100-2294 Rev 1
18
3.4.2 Power & Signal Wiring
1. Locate the relevant connections
(Power, Analog, Modbus)
and remove the terminal
block from the PCBA.
(The PCB terminal blocks are pluggable type and may be
removed to aid termination.)
Connection
Description
Label
Wiring Termination
Power
24 VDC/VAC IN
24V IN: -
24 VDC/VAC neutral /
ground
24V IN: +
24 VDC positive / VAC live
24 VDC/VAC OUT
(power daisy chain
terminal)
24V OUT: -
24 VDC/VAC neutral /
ground
24V OUT: +
24 VDC positive / VAC live
Digital Output
Modbus Network
Communications
MODBUS: B
RS-
485 “B”
(inverted)
MODBUS: A
RS-
485 “A”
(non-inverted)
MODBUS: GND
RS-485 GND
MODBUS: SH
RS-485 Shield
Analog Output
Voltage or Current
Output
ANALOG: -
Analog output ground
ANALOG: +
Analog output signal
(+)
2. Remove plugs from the corresponding M16 cable glands.
The product comes with cable glands and plugs pre-installed.
(The power entry
cable gland is shipped from the factory without a plug.)
3. Using the appropriate cable glands, insert wires into the enclosure.
4. Secure the wires in each terminal block and, pressing firmly, reinstall the terminal block
into the PCBA.
Polarity must not be reversed.
For 24 VAC installations in a daisy-chain configuration, the neutral polarity must
be maintained for all instruments.
5. Remove all excess cable from the housing before securing the cable glands.