1100-2294 Rev 1
49
2103
🔒
Stop Bits
Stop bits = 1 or 2
16-bit Unsigned
Integer
2104
🔒
Parity
0 = None, 1 = Odd, 2 = Even
2105
🔒
Enable 120ohm Termination
0 = No termination, 1 = termination enabled
Boolean
2106
🔒
Sensor Low Alarm
(PPM/PPB/VOL/LEL)
Low gas alarm in display units (Local Alarm set points
stored on controller, override sensor values)
16-bit Unsigned
Integer
2107
🔒
Sensor High Alarm
(PPM/PPB/VOL/LEL)
High gas alarm in display units (Local Alarm set
points stored on controller, override sensor values)
2108
🔒
Analog output Range
Set voltage output (0=1-5V, 1=0-5V, 2=0-10V, 3=4-
20mA, 4=2-10V) ( if hardware override - write
exception / read dip 2&3)
2109
🔒
Analog output Zero Adjust
Sets Analog output zero offset to allow output
calibration (in DAC codes)
2110
🔒
Analog output Span Adjust
Sets Analog output scaling factor to allow output
calibration (in % scaled by x10 ie 123 = 12.3%)
2111
🔒
Buzzer disable
0 = Buzzer normal operation, 1 = Buzzer disabled (if
hardware override - write exception / read dip 4)
Boolean
2112
🔒
Relay Contact Behavior /
Failsafe
0 = NO relay, 1 = Failsafe relay (if hardware override -
write exception / read dip 5)
2113
🔒
Alarm Latching Behavior
0 = Alarms automatically reset, 1 = Alarms must be
acknowledged (if hardware override - write exception /
read dip 6)
Boolean
2114
🔒
Alarm ON Delay (0-900)
seconds
Alarm on delay in seconds Range (0-900 secs), i.e. (0-
15 mins). (if hardware override - write exception/ read
dip 7)
16-bit Unsigned
Integer
2115
🔒
Alias Text Char 1,2
Alias Characters (16 char alias string =
"XXXXXXXXXXXXXXXX")
2116
🔒
Alias Text Char 3,4
Alias Characters (16 char alias string =
"XXXXXXXXXXXXXXXX")
2117
🔒
Alias Text Char 5,6
Alias Characters (16 char alias string =
"XXXXXXXXXXXXXXXX")
2118
🔒
Alias Text Char 7,8
Alias Characters (16 char alias string =
"XXXXXXXXXXXXXXXX")
2119
🔒
Alias Text Char 9,10
Alias Characters (16 char alias string =
"XXXXXXXXXXXXXXXX")
2120
🔒
Alias Text Char 11,12
Alias Characters (16 char alias string =
"XXXXXXXXXXXXXXXX")
2121
🔒
Alias Text Char 13,14
Alias Characters (16 char alias string =
"XXXXXXXXXXXXXXXX")
2122
🔒
Alias Text Char 15,16
Alias Characters (16 char alias string =
"XXXXXXXXXXXXXXXX")
2123
🔒
Unlock code
4-digit code used to unlock user settings (0000-9999),
numeric, can only be read/written if system is already
unlocked
16-bit Unsigned
Integer
2124
🔒
Bluetooth Passkey
6-digit Bluetooth passkey (000000-999999), numeric,
can only be read/written if system is unlocked,
requires power cycle to take effect
32-bit Unsigned
Integer
2125
🔒
6.4.4 Integration
– Calibration
Holding Register
(Function 03/06 Read / Write)
🔒
2200
Sensor Calibration gas
applied (PPM/PPB/VOL/LEL)
Concentration of calibration gas applied during
calibration (must be set before calibration if using gas
!= sensor nominal) set to sensor nominal on reset
16-bit Unsigned
Integer
Содержание MGS-400
Страница 1: ...1100 2294 Rev 1 1...