AB-6438
7
Wire Specifications
Item Wiring
Wiring
length*
1
Condition
Power supply*
2
JIS IV2.0 mm
2
or JIS CVV 2.0 mm
2
or greater
Ground*
2
JIS IV 2.0 mm
2
or JIS CVV 2.0 mm
2
or greater
Ground resistance: Max. 100
Ω
Digital input*
3
JIS IV, JIS CVV, or KPEV 0.9 mm
2
, 1.25 mm
2
50
m
Relay output*
3
JIS IV, JIS CVV, or KPEV 1.25 mm
2
50 m
Max. 30 V AC/DC
Temperature input*
3, 4
JIS IV, JIS CVV, or KPEV 1.25 mm
2
50
m
Voltage input*
3
JIS IV, JIS CVV, or KPEV 0.9 mm
2
, 1.25 mm
2
50
m
Voltage output*
3
JCS CVV-S 1.25 mm
2
20 m
Inverter output
JIS IV, JIS CVV, or KPEV 1.25 mm
2
10
m
Valve/damper
(for the system common wiring*
5
)
JIS IV, JIS CVV, or KPEV 2.0 mm
2
(from the relay terminal block)
20 m
JIS IV, JIS CVV, or KPEV 1.25 mm
2
20
m
Valve/damper
Communication
(NC-bus)*
3
JCS IPEV-S 0.9 mm
2
500
m
JCS: Japanese Electric Wire & Cable Makers' Association Standard
JIS: Japanese Industrial Standards
KPEV: Cable standard provided by Furukawa Electric Co., Ltd.
Notes:
*1 Wiring length shown above is the total wiring length from Infilex AC to a device in connection, including the wiring to and from an external
terminal block.
*2 Power supply and ground wires are connected to the M3 screw terminals. Crimp the terminal lugs on the wire ends.
*3 Communication and input/output wires are connected to the screwless push-in terminals. Strip the wire sheath and connect the wires.
Sheath strip length: 8 mm (Pin terminal cannot be used.)
*4 RTD (Pt1000) temperature input is two-wire. Take the measuring error into account because the wire resistance causes measuring error.
For instance, 1.25 mm
2
size wire causes approx. 0.1 °C measuring error every 10 m. Correct the measuring error by setting Infilex AC.
*5 When the valve/damper is connected for the system common wiring, the valve/damper operating current flows through the common line.
Hence, the specification is as shown above. For a 20 m long IV 1.25 mm
2
cable, 4-wire connection is necessary to prevent the operating
current from flowing through the common line.