Azbil Infilex AC WY5117C1 Series Скачать руководство пользователя страница 13

AB-6438 

13 

Wiring 

 WARNING  

 

Detach the terminal cover only when wiring the product.  Before detaching the terminal cover, be sure to turn off the 
power to the product and all the connected devices.  After wiring, be sure to reattach the terminal cover.  
Failure to do so might cause electric shock. 

 

Before wiring and maintenance, be sure to turn off the power to the product. 
Failure to do so might cause electric shock. 

 

 CAUTION 

 

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

 

All wiring must comply with applicable codes and ordinances. 

 

Firmly tighten the terminal screws.   
Insufficient tightening of the terminal screws might cause fire or overheating. 

 

For wiring, strip each wire insulation for the length specified in this manual.  If the strip length is longer than the 
specified, the stripped part of the wires will be exposed, causing electric shock or short circuit between adjacent 
terminals.  If it is shorter, the stripped part will not contact the connector. 

 

Do not use unused/spare terminals on the product as relay terminals. 
Doing so might cause malfunction. 

 

Do not block the ventilation holes of this product. (Be sure to peel off the protective sheet after installation and wiring).
Doing so might cause device failure. 

 

Precautions for wiring 

 Tube 

marker: 

Since Infilex AC adopts the screwless push-in terminals, wires are connected 
without crimping terminal lugs.  Therefore, if normal tube markers are used, 
they may come off when you disconnect the wires.  To prevent this, use the 
following Flat Tube Marker.  It is held on a wire by friction and thus does not 
come off easily. 

Flat Tube Marker 

Manufacturer 

Phoenix Contact  

Item number 

5880029 

Model TMC-3 
Applicable wire size 

0.4 mm

2

 to 2 mm

2

 

Package unit 

200 m/roll 

 2 

mm

2

 cable running outside the control panel: 

Use an external terminal block to switch to 1.25 mm

2

 cable inside the control panel. 

  Two wires for one terminal: 

Use an external terminal block to aggregate the wires.

 

 Fan 

ON/OFF: 

Use a small-power circuit (max. 60 V operating voltage and 1.5 A operating current) to turn on and off fan. 

  Signal wire for output to inverter: 

Use a shielded cable.

 

 

Power supply wiring 

Crimp M3 terminal lugs with insulation on the wire ends, and connect the wires to the power supply terminals. 

 

 

 

 

 

 

 

Figure 8.  Power supply wiring 

Power supply wires

Power supply 

terminals 

1

2

3

Connect.

Содержание Infilex AC WY5117C1 Series

Страница 1: ...compact AHU Wide range of input output I O combinations Model with the I O combination best suitable for the air conditioning controls you desire such as outdoor air cooling control humidification etc...

Страница 2: ...danger The symbol inside graphically indicates the actual action to be carried out For example the sign on the left indicates general instructions WARNING Be sure to ground the product with ground res...

Страница 3: ...minals If it is shorter the stripped part will not contact the connector Do not use unused spare terminals on the product as relay terminals Doing so might cause malfunction Do not block the ventilati...

Страница 4: ...sor Neoplate Model QY7290 Infilex ZM Model WY5122 Temperature sensor Neopanel Model QY7205 Temperature sensor Infilex VC Model WY5206 SC bus Max 50 units and 1000 m Infilex ZM Model WY5122 Infilex VC...

Страница 5: ...ital input 6 pts voltage output 5 pts relay output 5 pts 1 UT module or Operator Panel integral type connectable 1 2 4 Temperature input 2 pts voltage input 2 pts digital input 8 pts voltage output 6...

Страница 6: ...n collector Allowable contact ON resistance Max 100 Allowable contact OFF resistance Min 100 k Allowable ON residual voltage Max 1 V DC Temperature input Input signal RTD Pt100 100 0 C Pt1000 1000 0 C...

Страница 7: ...standard provided by Furukawa Electric Co Ltd Notes 1 Wiring length shown above is the total wiring length from Infilex AC to a device in connection including the wiring to and from an external termin...

Страница 8: ...e that can be added to Model WY5117C1400 refer to AB 6527 Specifications Instructions of Model RY50XX S S Fan ON OFF Fan ON OFF Humidifier Outdoor air damper Return air temperature Supply air temperat...

Страница 9: ...on of 0 25 second ON and 0 25 second OFF Major failure initializing ON Minor failure Repetition of 1 second ON 0 25 second OFF 0 25 second ON and 0 25 second OFF Engineering mode Repetition of 0 25 se...

Страница 10: ...ition Do not mount Infilex AC with the body tilted Always mount it in the positions as shown in the figure below No other mounting positions are allowed Upright Sideway allowed only when I O module UT...

Страница 11: ...e Notes 1 Pitch between upper lower cable duct and the DIN rail 2 Up to two modules I O module and or UT module integral type Operator Panel can be assembled with the basic unit 3 DIN rail position is...

Страница 12: ...th of I O module UT module or integral type Operator Panel Hatched area in the figure below shows the maintenance clearance Note Up to two modules I O module and or UT module integral type Operator Pa...

Страница 13: ...Doing so might cause malfunction Do not block the ventilation holes of this product Be sure to peel off the protective sheet after installation and wiring Doing so might cause device failure Precautio...

Страница 14: ...e fiber being disconnected from the terminal Note If you pull out the wire diagonally it may be disconnected Arrangement of the wires connected to Infilex AC Notes Neatly place the wires using cable t...

Страница 15: ...sion between Infilex AC and each device use wiring Figure 10 Wiring example System common wiring IMPORTANT Use an isolation transformer Do not ground the secondary side of the transformer Provide a te...

Страница 16: ...that the all the wires are correctly connected Remove the protective sheet from the top surface of Infilex AC Note if some foreign objects possibly come inside Infilex AC from the ventilation holes o...

Страница 17: ...Data Setter Model QY7211B Convert the D SUB connector to the mini DIN connector with the conversion cable Part No 83104995 001 At this time hold the male connector with the mark facing left and inser...

Страница 18: ...ce the remaining battery level cannot be checked by measuring the terminal voltage be sure to replace the battery every 5 years Replace the lithium battery with the power ON If the product has never o...

Страница 19: ...AB 6438 19 Blank page added for page editing purpose...

Страница 20: ...SHRAE 20 AB 6438 Rev 9 0 Jul 2017 Install this product in a panel cabinet This product complies with the following harmonised standards of the Electromagnetic Compatibility Directive EMCD and the Rest...

Отзывы: