AB-6438 

11 

DIN rail mount 

The following figure shows the mounting dimensions of Infilex AC on DIN rail. 
The width may vary depending on how many modules (I/O module, UT module, and integral type Operator Panel)*

1

 are 

assembled with the Infilex AC basic unit. 

Width of Infilex AC = 60 mm*

2

 + 30 mm*

3

 x n (quantity) 

Notes: 
*1  Regarding I/O modules, UT module, and the integral type Operator Panel that can be assembled with Infilex AC basic unit, refer to  

AB-6527 Specifications/Instructions of Model RY50XX

*2  Width of Infilex AC basic unit 
*3  Width of I/O module, UT module, or integral type Operator Panel 
 

Hatched area in the figure below shows the maintenance clearance. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes: 
*1  Pitch between upper/lower cable duct and the DIN rail. 
*2  Up to two modules (I/O module and/or UT module/integral type Operator Panel) can be assembled with the basic unit. 
*3  DIN rail position is shifted 5 mm downward from the center of Infilex AC. 

 

Figure 6.  Mounting dimensions (mm): DIN rail mount 

 

Mount and fix Infilex AC on DIN rail so that it does not fall from the DIN rail.  Check that the DIN rail holders of each module are 
pushed up and fixed on the DIN rail. 
Fasten the bilateral sides of Infilex AC with two DIN rail mounting brackets (Part No. 83104567-001, separate order is required). 

 

DIN rail mounting brackets for bilateral sides
Part No. 83104567-001

 

Cable 

duct

Cable 

duct

Infilex AC

(45

)     3

5

 

140 

(45)

 

(122.5)*

1

 

           (132.

5)*

1

 

Cable duct

20

20

92

(60)

(60)

Cable duct

65 75 

35 

DIN rail holder 

Infilex AC 

basic unit

 

DIN rail

Infilex AC

60 + 30 

 n 

Hook

5*

3

 

106

*2

Содержание Infilex AC WY5117C1 Series

Страница 1: ...compact AHU Wide range of input output I O combinations Model with the I O combination best suitable for the air conditioning controls you desire such as outdoor air cooling control humidification etc...

Страница 2: ...danger The symbol inside graphically indicates the actual action to be carried out For example the sign on the left indicates general instructions WARNING Be sure to ground the product with ground res...

Страница 3: ...minals If it is shorter the stripped part will not contact the connector Do not use unused spare terminals on the product as relay terminals Doing so might cause malfunction Do not block the ventilati...

Страница 4: ...sor Neoplate Model QY7290 Infilex ZM Model WY5122 Temperature sensor Neopanel Model QY7205 Temperature sensor Infilex VC Model WY5206 SC bus Max 50 units and 1000 m Infilex ZM Model WY5122 Infilex VC...

Страница 5: ...ital input 6 pts voltage output 5 pts relay output 5 pts 1 UT module or Operator Panel integral type connectable 1 2 4 Temperature input 2 pts voltage input 2 pts digital input 8 pts voltage output 6...

Страница 6: ...n collector Allowable contact ON resistance Max 100 Allowable contact OFF resistance Min 100 k Allowable ON residual voltage Max 1 V DC Temperature input Input signal RTD Pt100 100 0 C Pt1000 1000 0 C...

Страница 7: ...standard provided by Furukawa Electric Co Ltd Notes 1 Wiring length shown above is the total wiring length from Infilex AC to a device in connection including the wiring to and from an external termin...

Страница 8: ...e that can be added to Model WY5117C1400 refer to AB 6527 Specifications Instructions of Model RY50XX S S Fan ON OFF Fan ON OFF Humidifier Outdoor air damper Return air temperature Supply air temperat...

Страница 9: ...on of 0 25 second ON and 0 25 second OFF Major failure initializing ON Minor failure Repetition of 1 second ON 0 25 second OFF 0 25 second ON and 0 25 second OFF Engineering mode Repetition of 0 25 se...

Страница 10: ...ition Do not mount Infilex AC with the body tilted Always mount it in the positions as shown in the figure below No other mounting positions are allowed Upright Sideway allowed only when I O module UT...

Страница 11: ...e Notes 1 Pitch between upper lower cable duct and the DIN rail 2 Up to two modules I O module and or UT module integral type Operator Panel can be assembled with the basic unit 3 DIN rail position is...

Страница 12: ...th of I O module UT module or integral type Operator Panel Hatched area in the figure below shows the maintenance clearance Note Up to two modules I O module and or UT module integral type Operator Pa...

Страница 13: ...Doing so might cause malfunction Do not block the ventilation holes of this product Be sure to peel off the protective sheet after installation and wiring Doing so might cause device failure Precautio...

Страница 14: ...e fiber being disconnected from the terminal Note If you pull out the wire diagonally it may be disconnected Arrangement of the wires connected to Infilex AC Notes Neatly place the wires using cable t...

Страница 15: ...sion between Infilex AC and each device use wiring Figure 10 Wiring example System common wiring IMPORTANT Use an isolation transformer Do not ground the secondary side of the transformer Provide a te...

Страница 16: ...that the all the wires are correctly connected Remove the protective sheet from the top surface of Infilex AC Note if some foreign objects possibly come inside Infilex AC from the ventilation holes o...

Страница 17: ...Data Setter Model QY7211B Convert the D SUB connector to the mini DIN connector with the conversion cable Part No 83104995 001 At this time hold the male connector with the mark facing left and inser...

Страница 18: ...ce the remaining battery level cannot be checked by measuring the terminal voltage be sure to replace the battery every 5 years Replace the lithium battery with the power ON If the product has never o...

Страница 19: ...AB 6438 19 Blank page added for page editing purpose...

Страница 20: ...SHRAE 20 AB 6438 Rev 9 0 Jul 2017 Install this product in a panel cabinet This product complies with the following harmonised standards of the Electromagnetic Compatibility Directive EMCD and the Rest...

Отзывы: