Specifications/Instructions

 

Infilex

 AC 

Air Handling Unit Controller 

for NC-bus Communication 

 
General 

Infilex AC Model WY5117C1XXX is a DDC controller for AHU.  
It is installed in a small space such as an AHU control panel. 

Infilex AC is equipped with inputs and outputs suitable for 
AHU control, and its software is freely editable in response to 
the applications. 

Operator interface and room user terminal are connectable to 
Infilex AC, supporting you in various situations to operate 
Infilex AC. 

Infilex AC also is networked with our BMS via our proprietary 
protocol NC-bus.  Infilex AC sends operating status to the 
BMS and performs operating management in accordance 
with the commands sent from the BMS in order for you to 
integrally control and manage a whole building.   

The time scheduling function of Infilex AC, on the other hand, 
enables autonomous-distributed control.  

 
AHU: Air handling unit 
BMS: Building management system 
DDC: Direct digital control 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features 

 Compact 

design: 

Small sized body fits inside a control panel of a compact 
AHU. 

  Wide range of input/output (I/O) combinations: 

Model with the I/O combination best-suitable for the air 
conditioning controls you desire, such as outdoor air 
cooling control, humidification, etc. is selectable. 

  Increase in I/O points: 

An I/O module is added to Model WY5117C140X for 
increasing the I/O points. 

  Operator interface (Operator Panel): 

Operator Panel (panel mount type/integral type) 
connected to Infilex AC allows you to change the settings 
of Infilex AC without accessing Infilex AC from the BMS. 

  Room user terminals: 

User terminal (Neopanel or Neoplate) is connectable to 
Infilex AC, enabling the room occupants to turn on/off air 
conditioning unit and change temperature setting.

 

 

 Cooperation 

with 

BMS: 

Infilex AC is networked with our BMS to centrally monitor 
and control AHU

.

 

  Autonomous distributed control: 

Even if a trouble occurs in the BMS, Infilex AC 
individually performs backup operation to distribute 
potential risks caused by malfunction of the BMS. 

 Installation: 

Screwless push-in terminals for I/O reduce wiring 
workload.   
Additionally, either DIN rail mount or screw mount is 
selectable. 

  CE Marking certified product: 

Infilex AC Model WY5117C conforms to all the 
applicable standards of CE Marking. 

 
DIN: Deutsches Institut fur Normung (German Institute for 
Standardization) 

 

 

Содержание Infilex AC WY5117C1 Series

Страница 1: ...compact AHU Wide range of input output I O combinations Model with the I O combination best suitable for the air conditioning controls you desire such as outdoor air cooling control humidification etc...

Страница 2: ...danger The symbol inside graphically indicates the actual action to be carried out For example the sign on the left indicates general instructions WARNING Be sure to ground the product with ground res...

Страница 3: ...minals If it is shorter the stripped part will not contact the connector Do not use unused spare terminals on the product as relay terminals Doing so might cause malfunction Do not block the ventilati...

Страница 4: ...sor Neoplate Model QY7290 Infilex ZM Model WY5122 Temperature sensor Neopanel Model QY7205 Temperature sensor Infilex VC Model WY5206 SC bus Max 50 units and 1000 m Infilex ZM Model WY5122 Infilex VC...

Страница 5: ...ital input 6 pts voltage output 5 pts relay output 5 pts 1 UT module or Operator Panel integral type connectable 1 2 4 Temperature input 2 pts voltage input 2 pts digital input 8 pts voltage output 6...

Страница 6: ...n collector Allowable contact ON resistance Max 100 Allowable contact OFF resistance Min 100 k Allowable ON residual voltage Max 1 V DC Temperature input Input signal RTD Pt100 100 0 C Pt1000 1000 0 C...

Страница 7: ...standard provided by Furukawa Electric Co Ltd Notes 1 Wiring length shown above is the total wiring length from Infilex AC to a device in connection including the wiring to and from an external termin...

Страница 8: ...e that can be added to Model WY5117C1400 refer to AB 6527 Specifications Instructions of Model RY50XX S S Fan ON OFF Fan ON OFF Humidifier Outdoor air damper Return air temperature Supply air temperat...

Страница 9: ...on of 0 25 second ON and 0 25 second OFF Major failure initializing ON Minor failure Repetition of 1 second ON 0 25 second OFF 0 25 second ON and 0 25 second OFF Engineering mode Repetition of 0 25 se...

Страница 10: ...ition Do not mount Infilex AC with the body tilted Always mount it in the positions as shown in the figure below No other mounting positions are allowed Upright Sideway allowed only when I O module UT...

Страница 11: ...e Notes 1 Pitch between upper lower cable duct and the DIN rail 2 Up to two modules I O module and or UT module integral type Operator Panel can be assembled with the basic unit 3 DIN rail position is...

Страница 12: ...th of I O module UT module or integral type Operator Panel Hatched area in the figure below shows the maintenance clearance Note Up to two modules I O module and or UT module integral type Operator Pa...

Страница 13: ...Doing so might cause malfunction Do not block the ventilation holes of this product Be sure to peel off the protective sheet after installation and wiring Doing so might cause device failure Precautio...

Страница 14: ...e fiber being disconnected from the terminal Note If you pull out the wire diagonally it may be disconnected Arrangement of the wires connected to Infilex AC Notes Neatly place the wires using cable t...

Страница 15: ...sion between Infilex AC and each device use wiring Figure 10 Wiring example System common wiring IMPORTANT Use an isolation transformer Do not ground the secondary side of the transformer Provide a te...

Страница 16: ...that the all the wires are correctly connected Remove the protective sheet from the top surface of Infilex AC Note if some foreign objects possibly come inside Infilex AC from the ventilation holes o...

Страница 17: ...Data Setter Model QY7211B Convert the D SUB connector to the mini DIN connector with the conversion cable Part No 83104995 001 At this time hold the male connector with the mark facing left and inser...

Страница 18: ...ce the remaining battery level cannot be checked by measuring the terminal voltage be sure to replace the battery every 5 years Replace the lithium battery with the power ON If the product has never o...

Страница 19: ...AB 6438 19 Blank page added for page editing purpose...

Страница 20: ...SHRAE 20 AB 6438 Rev 9 0 Jul 2017 Install this product in a panel cabinet This product complies with the following harmonised standards of the Electromagnetic Compatibility Directive EMCD and the Rest...

Отзывы: