AB-7050
14
Installation steps: Neosensor in Multi-Thermocase with Multi-Thermocase mounting kit
1) Attach the main unit of the Multi-Thermocase mounting kit to the device mounting plate of Multi-Thermocase.
2) Connect the lead wires of Neosensor to the wires from the load.
Note:
The number of the lead wires differs depending on the models. Note that the Pt100 temperature sensor model with modular connection
has a modular jack instead of lead wires. (Model TY7043Z0P01(-1))
3) Remove the cover from the Neosensor main unit as shown in Fig. 14.
4) Set the depth change levers on the bilateral sides of the Neosensor main unit to the lower position (indicated with "H").
5) Mount the Neosensor main unit to the Multi-Thermocase mounting kit with four screws (M3
×
16) supplied with the
Neosensor. In the Multi-Thermocase, Neosensor is installed with its cover removed.
IMPORTANT:
Before installing Neosensor in the Multi-Thermocase, be sure to set the depth change levers on the bilateral
sides of the Neosensor main unit at the lower position (indicated with “H”.)
Figure 13. Installation: Neosensor (in Multi-Thermocase) with Multi-Thermocase mounting kit
Device mounting plate
of Multi-Thermocase
Multi-Thermocase
Depth change levers at
the lower position (indicated with “H”).
Note:
Lower the depth change levers at "H" position first, then assemble the
Neosensor main unit (without the cover) with the Multi-Thermocase
mounting kit and fix with the four screws (Neosensor accessory).
Device mounting plate
of Multi-Thermocase
External wires
from the load
66.7 mm
Main unit of
Multi-Thermocase mounting kit
2 pan-head machine screws (M3
×
6)
of Multi-Thermocase
Main unit of Neosensor
4 flat-head machine screws
(M3
×
16) of Neosensor
Neosensor
(with the cover removed)
Multi-Thermocase mounting kit
(optional)
Set at the
lower position
Set at the
lower position
Lead wires of Neosensor