CAUTION
Use the product under the operating conditions (temperature, humidity, power, vibration, shock, mounting direction,
atmospheric condition, etc.) as listed in the specifications.
Failure to do so might cause fire or device failure.
Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.
Requirements for installation location
IMPORTANT:
●
Installation location of Neosensor largely affects temperature/humidity control. Carefully select the location.
●
Chemical (organic solvent) atmosphere may shift the output values.
●
Corrosive gas, organic solvent, and other chemicals contained in the atmosphere can cause measuring error
of Neosensor, shorten the service life of Neosensor, or damage Neosensor.
Ask our salesperson for use of Neosensor in a special application, as mentioned above.
Install Neosensor on an indoor wall where:
●
Representative temperature and humidity (of the room/zone to control) are measured (approx. 1.5 m high above the floor).
●
Ambient air velocity is 0.1 to 0.15 m/s.
●
There is enough maintenance space left in front of Neosensor.
Do not install Neosensor on a wall where:
●
Heat (generated by office device or equipment, for example) stays on.
●
Air circulation is interfered (by furniture or door, for example).
●
Temperature and/or humidity sensing is affected by draft, downdraft, and hot/cold air from water pipes/ducts.
●
Temperature and/or humidity sensing is affected by weather conditions (including sunlight and outdoor air).
●
There is vibration.
●
Dew condensation occurs.
●
Water
drops.
●
Corrosive gas, organic solvent, or other chemicals is contained in the atmosphere.
Do not install Neosensor outdoors or in a duct.
Do not horizontally install Neosensor directly on a ceiling surface.
Precautions for installation
●
Install Neosensor with a dedicated mounting kit (sold separately) suitable for your application.
●
Do not allow any refuse such as an electric wire scrap to get inside Neosensor.
●
Do not get a cable caught between the Neosensor main unit and the mounting surface.
●
Carefully handle Neosensor when the cover is removed so that the element does not get damaged.
●
Check that the ambient air velocity is sufficient in a location (not on a ceiling surface) where Neosensor will be horizontally
installed.
●
If air infiltrates to the rear side of the Neosensor from the inside of the installed wall through the outlet box, shut off the air by
sealing the outlet box.
●
After installation, leave Neosensor well so that it adapts to ambient conditions (atmospheric environment).