background image

AB-7050 

18 

24 V DC transformer: Multiple Neosensor powered by a single transformer (correct example) 
Multiple Neosensor or a Neosensor and another device in connection can be powered by a single 24 V DC power.  

 

 

 

 

 

 

 

 

 

 

Figure 24.  Good wiring example: Two Neosensor (temperature/humidity sensors) powered by a single 24 V DC transformer 

 

Notes for signal wiring 

Induction current flowing from Neosensor (humidity sensor, temperature/humidity sensor models) to the controller input circuit 
and inadequate time constant of the controller might generate noise.  To prevent noise, see the following. 

 

Use a controller with low pass filter (40 dB or higher removal ratio in normal mode) that receives signals from Neosensor. 

 

For insufficient removal ratio, provide an isolator on the controller input wiring. 

Note: 
 

No problem will occur for connecting Neosensor to our controller. 

 

 

IMPORTANT: 

  When Neosensor is faulty, reduced output may cause over-humidification.  Provide safety measure against 

over-humidification. 

  Corrosive gas or organic solvent contained in the air may cause sensing error, shorten the service life, or 

damage the Neosensor.  Before using Neosensor in abnormal atmosphere, consult with our salesperson. 

Though common wiring forms a loop, common mode noise affects a little. 

24 V DC 

Temperature/humidity sensor

Temperature/humidity sensor Controller

Good wiring 

+

+

+

+

Содержание HTY7043T1P00

Страница 1: ...sing Neosensor is thus suitable for various applications such as commercial building air conditioning or other indoor uses Note The specification data of the two wire 4 20mA output model of Neosensor...

Страница 2: ...bligatory action to prevent possible danger The symbol inside graphically indicates the actual action to be carried out For example the sign on the left indicates general instructions CAUTION Use the...

Страница 3: ...ow Available model numbers Model number Type Power Humidity output Temperature output Signal output wire connection Company logo HTY7043T1P00 Yes HTY7043T1P00 1 Neosensor 24 V DC AC 1 5 VDC RTD Pt100...

Страница 4: ...iring Thermoplate for open wiring is used for open wiring installation Part No DY2000A3021 For mounting three Neosensor crosswise Auxiliary device Multi Thermocase Model TY1100Z LAN cable Part No DY72...

Страница 5: ...tion resistance Min 500 V DC 20 M Withstand voltage 500 V AC applied for 1 min with max of 1 mA leakage current between housing and terminals Environmental conditions Rated operating condition Limit o...

Страница 6: ...tead of lead wires Model TY7043Z0P01 1 Figure 1 Mounting dimensions mm Neosensor with Wall direct mounting kit Neosensor high sensitive type Note For wiring secure more than 15 mm clearance inside the...

Страница 7: ...unting surface when installing Neosensor with Thermoplate mounting kit 2 The number of lead wires differs depending on the models Note that the Pt100 temperature sensor model with modular connection h...

Страница 8: ...th Thermoplate mounting kit Figure 5 Mounting dimensions mm Neosensor high sensitive type with Thermoplate mounting kit on Thermoplate Thermoplate mounting kit Figure 6 Dimensions mm Mounting plate of...

Страница 9: ...sensor model with modular connection has a modular jack instead of lead wires Model TY7043Z0P01 1 Figure 7 Mounting dimensions mm Neosensor not covered with Multi Thermocase mounting kit Multi Thermoc...

Страница 10: ...rated by office device or equipment for example stays on Air circulation is interfered by furniture or door for example Temperature and or humidity sensing is affected by draft downdraft and hot cold...

Страница 11: ...14 5 Set the depth change levers on the bilateral sides of the Neosensor main unit to the upper position indicated with L shown in Fig 17 6 Mount the main unit of Neosensor on the main unit of the Wa...

Страница 12: ...d with L shown in Fig 17 6 Mount the main unit of Neosensor on the main unit of the Wall direct mounting kit with four mounting screws M3 16 supplied with Neosensor 7 Attach the cover back to the Neos...

Страница 13: ...on the bilateral sides of the Neosensor main unit to the upper position indicated with L shown in Fig 17 7 Mount the main unit of Neosensor on the main unit of the Thermoplate mounting kit with four...

Страница 14: ...lled with its cover removed IMPORTANT Before installing Neosensor in the Multi Thermocase be sure to set the depth change levers on the bilateral sides of the Neosensor main unit at the lower position...

Страница 15: ...pth change Raising the Neosensor main unit 3 Set the depth change levers located on the bilateral sides on the main unit front surface at the lower position The levers are factory set at the upper pos...

Страница 16: ...ck Blue Black 24 V AC DC 1 5 V DC 0 10 V DC Power supply Humidity Models HY7043T1000 1 and HY7043T6000 1 Figure 22 Terminal wiring Humidity sensor with 1 5V 0 10V humidity output 24 V AC DC power Pt10...

Страница 17: ...sor temperature humidity sensor models IMPORTANT Use isolated transformer to supply 24 V AC power Single Neosensor must be powered by a single 24 V AC transformer If the multiple Neosensor or a Neosen...

Страница 18: ...wing Use a controller with low pass filter 40 dB or higher removal ratio in normal mode that receives signals from Neosensor For insufficient removal ratio provide an isolator on the controller input...

Страница 19: ...ration Neosensor is factory calibrated and does not require field calibration right after installation However field calibrate Neosensor if a shift in the output due to aged deterioration is found For...

Страница 20: ...ademark of Azbil Corporation in Japan or in other countries Specifications are subject to change without notice Building Systems Company http www azbil com Rev 2 0 Sep 2015 AB 7050 J AI 7050 Rev 3 2 P...

Отзывы: