UMAX090600 Version 1
Preliminary Documentation – May be Subject to Change
36-48
Name Range
Default
Notes
Bulk Charge Stage Voltage Threshold
5V to Limit
11.5V
Limit = Absorption Stage Voltage
Threshold
Absorption Stage Voltage Threshold
Limit to 16V
14.2V
Limit = Bulk Charge Stage Voltage
Threshold
Float Stage Current Threshold
0mA to 750mA
200mA
Float to Bulk Transition Voltage Threshold
Limit1 to Limit2
13.1V
Limit1 = Bulk Charge Stage
Voltage Threshold
Limit2 = Float Stage Voltage Level
Pre-Charge Stage Current Level
0 to 1000mA
400mA
Bulk Charge Stage Current Level
0 to 2000mA
2000mA
Absorption Charge Stage Voltage Level
Limit to 16V
14.2V
Limit = Bulk Charge Stage Voltage
Threshold
Float Stage Voltage Level
Limit to 16V
13.8V
Limit = Float to Bulk Transition
Voltage Threshold
Voltage Hysteresis Value
0 to 5V
0.2V
Used for all thresholds or levels
Current Hysteresis Value
0 to 500 mA
100 mA
Used for all thresholds or levels
4.4.
Constant Data List Setpoints
The Constant Data List function block is provided to allow the user to select values as desired for
various logic block functions.
The first two constants are fixed values of 0 (False) and 1 (True) for use in binary logic. The remaining
8 constants are fully user programmable to any value b/- 1,000,000. The default values
(shown below) are arbitrary and should be configured by the user as appropriate for their application.
Screen Capture of Default Constant Data List Setpoints