AVE RegCom-Pro Скачать руководство пользователя страница 78

78

MASTER COMMUNICATION PROTOCOL

OPERATION

The RegCom-Pro or Hydra/Regcom/Vnetworker/Networker use a bi-directional, 2-wire RS-485 databus to communicate.
A RegCom-Pro can be a Slave or a Master. A Regcom, Vnetworker or Networker are used to convert the VSI-Pro, ECR
Cards or Adapters to be slaves. The Hydra is a “Master” device and only one unit required for up to 16 Slaves. Only one
master device can exist on a single network. When the RegCom-Pro is used to connect to a register that uses the
emulate mode then it can not be a Master. However the RegCom-Pro can connect to a normal register in tap mode and
still be configurable as a master or slave.

The master device controls the flow of data by polling each of the slaves in turn. When polled, a slave device will
either respond with a ‘‘No Data’’ code to say it has no data to send, or it will begin sending data from its buffer.

The Hydra or RegCom-Pro  can support many manufactures of DVR for direct storage of the transaction data on the
DVR as a file rather than just inserting in the video image for recording. It also supports the VSI-ADD (VSI Addressable)
format which allows multiple VSI-Pros or RegCom-Pro to be mounted in a convenient rack and connected to a Master
for display of cash register data remotely. See Figure below.

HYDRA COMPATABILITY LIST

DVR

 

Norbain Columbus

 

GE StoreSafe

 

Kalatel StoreSafe

 

NOVAR VP

 

Dallmeier

 

Appro

 

Pinetron

Figure 142: DS-20-OF RegCom-Pro PCB Rack using VSI-ADD protocol

MASTER / HYDRA

 APPENDIX M

 RegCom-Pro  POS / Cash Register Interface

Pair 3 

Pair 2 

Pair 4  Pair 1 

T568B 

The Network Port of a RegCom-Pro, Regcom or Hydra use an RJ45 connector. Each unit has two RJ45s and the
Networking signals Pins 4&5 are in parallel. However in the RegCom-Pro all pins are wired in parallel but the Regcom
or Hydra are not. The useage of an RJ45 connector allows the installer to use either RJ11, RJ12 or RJ45 connectors
since all support the center two pins of the connector which are the only pins used.

Figure 141  : RJ45 Network Connector Pin Out

Содержание RegCom-Pro

Страница 1: ...R R R R Re e e e egCom Pr gCom Pr gCom Pr gCom Pr gCom Pro o o o o POS CASH REGISTER INTERFACE Operation Manual April 2010...

Страница 2: ...RE INSIDE REFER SERVICING TO QUALIFIED PERSONNEL CAUTION RISK OF ELECTRICAL SHOCK DO NOT OPEN WARNING THIS EQUIPMENT GENERATES USES AND CAN RADIATE RADIO FRE QUENCY ENERGY AND IF NOT INSTALLED AND USE...

Страница 3: ...8 Registers A Z 18 29 4 4 Time Date Display 30 Set Time Date 31 4 5 Text Display 31 Output Characters per Line 31 4 6 Communication 32 Register Settings 33 Interface Type 33 RX Baudrate 33 TX Baudrate...

Страница 4: ...f the DB 9 Female Connector on the RegCom ProRS 232 12 Table 2 RS 232 DB 9 Pin Out vs RegCom Pro DB 9 Pin Out 12 Table 3 Pin Out of the DB 9 Female Connector on the RegCom Pro RS 422 RS 485 13 Table 4...

Страница 5: ...Converter 71 Appendix K TCIP232Adapter 72 Appendix L RegCom Pro Networking 73 Appendix M Network Communication and Configuration 74 Hydra Regcom 76 Master Protocol VSI ADD 77 Vnetworker Connections 7...

Страница 6: ...6 CONTENTS RegCom Pro POS Cash Register Interface...

Страница 7: ...7 CONTENTS RegCom Pro POS Cash Register Interface...

Страница 8: ...entral location PC Windows based software can also be used as the controller of this network and store transaction files for up to 16 cash registers for remote viewing or downloading to produce report...

Страница 9: ...e Date Format Automatic Daylight Savings Adjustment and Register T D Locking 800 Lines of Exception History Buffer 16 Triggered Text associated with 16 virtual alarms 2 Built in Programmable Hard Alar...

Страница 10: ...in 7 RTS Closure to Ground 12 VDC Max Real Time Clock 12 or 24 Hr with Auto Daylight Savings Time Programmable Date Format MM DD YY DD MM YY YY MM DD Julian Calendar Line Processing Compress Truncate...

Страница 11: ...egCom Pro Front Indicator LEDs 3 1 LED Indicators Power Green Signifies power is supplied to the unit Network LED Green This LED flashes whenever data is sent or received on the Network Port Register...

Страница 12: ...m Cash Register 3 Transmit Data From RegCom Pro Data to Cash Register 4 DTR From RegCom Pro Remain High or RS 485 Input A 5 Ground Signal Power Gnd or Isolated RS 232 Input Gnd 6 DSR From RegCom Pro R...

Страница 13: ...o 8 CTS From RegCom Pro 9 Alarm Out 2 Open Collector Transistor PIN FUNCTION DIRECTION Note When the RS 485 port is set for Bi Directional RS 485 the TXD port has no function When the RS 485 port is s...

Страница 14: ...signal ground and earth ground isolation Proper shielding of RS 232 signals will extend the length of wiring especially at high data rates and eliminate noise being coupled into the either a source o...

Страница 15: ...nd the RegCom Pro will self configure However if the RegCom Pro is already set to a baud rate you must select the exact baud rate and communication configuration in the RegCom Pro for connection to oc...

Страница 16: ...cess then you can do any function on this menu screen Upload data which reads the current settings of the RegCom Pro into the PC Download which sends the PC settings to the RegCom Pro Set Time can set...

Страница 17: ...19 2K so the RegCom Pro will communicate TCP IP Limitations The TCPIP232 Adapter can monitor any Ethernet LAN either 10MBs or 100MB s However the actual long term throughput of the adpater is limited...

Страница 18: ...O menu CASIO Select REGISTER SELECT Tab then select CASIO in drop down menu The CASIO menu will appear GENERIC Select REGISTER SELECT Tab then select GENERIC in drop down menu No menu will apprear and...

Страница 19: ...elect RS 232 PORT then sub menu will appear CASIO TE4000 Select REGISTER SELECT Tab then select CASIO in drop down menu and then select TE4000 The CASIO TE4000 sub menu will appear CASIO TE4500 Select...

Страница 20: ...SSER WAYNE in drop down menu TheDRESSER WAYNE menu and sub menu will appear Figure 27 DRESSER WAYNE menu EPSON GENERIC Select REGISTER SELECT Tab then select EPSON GENERIC in drop down menu The EPSON...

Страница 21: ...ces JOURNAL RECEIPT MIXED IBM 3151 TERMINAL Select REGISTER SELECT Tab then select IBM in drop down menu and then select IBM3151 TERMINAL The IBM3151 TERMINAL sub menu will appear IBM RDS Select REGIS...

Страница 22: ...es 000 001 002 999 ANYADDRESS Choices ON OFF Figure 39 I CNTRL INT JAVELIN VIPER menu I CNTRL INT JAVELIN VIPER Select REGISTER SELECT Tab then select I CNTRL INT JAVELIN VIPER in drop down menu The I...

Страница 23: ...EGISTER SELECT Tab then select MICROS in drop down menu and then select MICROS ISN NET WORK The MICROS ISN NETWORK sub menu will appear Figure 44 MICROS ISN NETWORK sub menu SOURCE TYPE Choices ANY 00...

Страница 24: ...LE sub menu OMEGA 2000 Select REGISTER SELECT Tab then select OMEGA 2000 in drop down menu The OMEGA 2000 menu will appear Figure 47 NCR 7059 sub menu NCR 7059 Select REGISTER SELECT Tab then select N...

Страница 25: ...CLARITY SMARTPAD Select REGISTER SELECT Tab then select PARA GON CLARITY SMARTPAD in drop down menu The PARAGON CLARITY SMARTPAD menu will appear Figure 55 PAR menu SET TERM NO Choices ALL 1 2 3 255 P...

Страница 26: ...0 sub menu Figure 62 SHARP UP600 700 sub menu SHARP UP600 700 Select REGISTER SELECT Tab then select SHARP in drop down menu and then select UP600 700 TheSHARP UP600 700 sub menu will appear 4 PROGRAM...

Страница 27: ...999 RegCom Pro POS Cash Register Interface 4 PROGRAMMING Figure 65 SICOM menu SICOM Select REGISTER SELECT Tab and select SICOM in drop down menu The SICOM menu will appear SECNETADDRESS Choices ANY...

Страница 28: ...F UNIWELL DX890 915 Select REGISTER SELECT Tab then select UNIWELL in drop down menu and then select DX890 915 The UNIWELL DX890 915 sub menu will appear Figure 75 UNIWELL DX890 915 sub menu 4 PROGRAM...

Страница 29: ...n select UNIWELL in drop down menu and then select SX875 8000 8500 The UNIWELL SX875 8000 8500 sub menu will appear UNIWELL UX60 Select REGISTER SELECT Tab then select UNIWELL in drop down menu and th...

Страница 30: ...is the same as the ATM time and date format If the T D LOCKING is turned on make sure that the time format selected is the same as the register s time date format If the T D LOCKING is turned on the R...

Страница 31: ...e Date Setting Page 4 5 TEXT DISPLAY This page will give you more control over the actual text block formatting and its appearance on the monitor To access the page Select TEXT SETUP Tab The following...

Страница 32: ...ined here When you choose your register type under the REGISTER SELECT menu this automatically formats the RegCom Pro to the appropriate settings needed to communicate with your register There may be...

Страница 33: ...menu Figure 85 Register Settings menu REGISTER SETTINGS The Register Settings selects and allows you to program the communication and protocol parameters used to communicate with the POS or Cash Regis...

Страница 34: ...rted by the AVE MVDR line of DVRs The Dallmeier setting supports communication to the Dallmeier DVR in Commanding mode ASCII is not supported in the Master mode selection PARITY Choices NONE ODD EVEN...

Страница 35: ...with the selected format is sent out the DB9 TXD Pin 3 for RS 232 In the RS 232 mode you can still use the RegCom Pro to interface to a POS or Cash Register but only in the tap mode using the DB9 RXD...

Страница 36: ...rogram remote RegCom Pro devices receive remote alarming and Time Date information BAUDRATE Choices 1200 115200 baud rate This sets the comunication speed for the Network port in all configurations Ca...

Страница 37: ...exceptions For example all transactions over 100 between 8 00 and 25 00 or lower than 10 and greater than 25 00 all transactions by a specific cashier or whatever transactions you need to watch excep...

Страница 38: ...ut can be connected to the other equipment such as DVRs computers phone line transmissions or digital storage devices for later retrieval The RegCom Pro also has a triggered text feature This feature...

Страница 39: ...Com Pro will self configure However if the RegCom Pro is already set to a baud rate you must select the exact baud rate and communication configuration in the RegCom Pro for connection to occur If the...

Страница 40: ...and save as a text file on the PC Figure 91 Example of Exception History Figure 90 PC and RegCom Pro Can Establish a Communication NOTE For any exception you must program History Buffer ON for any exc...

Страница 41: ...ection will appear RegCom Pro POS Cash Register Interface 4 PROGRAMMING SET EXCEPTION Select EXCEPTION REPORT Tab The SET EXCEPTION section will appear Figure 94 Set Exception Section EXCEPTION NO Cho...

Страница 42: ...on EXCEPTION STRING SETUP will appear again then click on CLEAR button and then program correct exception string in the blank HISTORY BUFFER Choices ON OFF The history buffer stores all the exceptions...

Страница 43: ...PROGRAMMING Figure 95 Exception String Section NOTE Remember to enter your Exception String based on the way that data prints to remote monitor including spaces NOTE Only 40 characters are allowed in...

Страница 44: ...rect range again 4 PROGRAMMING Figure 96 Set Range Section OPERATOR Choices NONE IN OUT The Operator determines the behavior of the Range Think of the Operator in mathematical terms Setting the correc...

Страница 45: ...etween 50 and 100 dollars will be flagged IN RANGE Suppose Exception 5 would flag all transactions between 50 00 100 00 on Department 3 Exception No 3 Output ON or OFF Depending on presence of serial...

Страница 46: ...send data to the serial printer When ON is selected all the data will be send to the serial printer regardless of what setting of output has selected in the individual output in set exception section...

Страница 47: ...e all Scroll Matching On changes the way the RegCom Pro processes exceptions Scroll matching only works with adver tising messages that are scrolling in the video by typically shifting accross a custo...

Страница 48: ...4 PROGRAMMING NOTE The ALARM OUTPUTS Page controls the formatting of the external alarms 4 8 ALARM OUTPUTS To access alarm output Select ALARM OUTPUTS Tab ALARM OUTPUTS section and TRIGGER TEXT sectio...

Страница 49: ...input if you are not using the handshaking function A contact closure to ground on pin 7 will trigger this alarm Coupled with the RTS Triggered text you can now display a 40 character message from an...

Страница 50: ...it is triggered The selections for alarm duration are PULSE 1 3 5 10 15 20 30 60 120 180 and 240 seconds PULSE sends a 200mS alarm pulse to the alarm device To select the amount of time in seconds tha...

Страница 51: ...UTS Tab then select TRIGGERED TEXT section and then select ON or OFF in OUTPUT TEXT drop down menu Selecting OFF will not send any exception text to the serial printer RTS TRIGGERED DELAY Choices OFF...

Страница 52: ...egCom Pro s capabilities with just a monitor and camera without having a register hooked up When the demo mode is active the RegCom Pro thinks the data is actually coming from a real register You can...

Страница 53: ...inuously work until disabled by cancel this selection If you connect the RegCom Pro to a cash register and it sends data to the RegCom Pro during this demo mode then the demo mode will also be disable...

Страница 54: ...xceptions and trigger strings quickly and easily This is accomplished by using a Com port of the laptop or a USB to RS 232 adapter Auto connection time out and error recovery guarantees the RegCom Pro...

Страница 55: ...et any baud rate and the RegCom Pro will self configure However if the RegCom Pro is already set to a baud rate you must select the exact baud rate and communication configuration in the RegCom Pro fo...

Страница 56: ...d the PC and or the RegCom Pro has a 30 second timeout and will reset itself for normal operation 4 PROGRAMMING Figure 110 PC and RegCom Pro Can Establish a Communication Once you have Access then you...

Страница 57: ...ics of the RegCom Pro Program Download Ver 1 0 RegCom Pro Manual is an online pdf of the current RegCom Pro manual for easy reference to all the setups and programming features and applications of the...

Страница 58: ...uP via a conventional programmer Then the executable program is then loaded via any terminal program such as Hyper Terminal via a PC or compatible device All firmware files are encoded to the AVE pro...

Страница 59: ...lick File Properties You will see the configuration frame and then click Figure 115 Connect To Menu Figure 116 Port Settings Menu RegCom Pro POS Cash Register Interface Choose Bits per second to 19200...

Страница 60: ...have to send file to update firmware by click on Transfer Menu and select Send Text File and wait until finished programming Progress dots will be displayed on the terminal program until finished and...

Страница 61: ...V1 0 After installation is complete run the program The following window will be loaded Connection diagram of RegCom Pro Network and DVR Figure 117 RegCom Pro Network and DVR Connections Figure 117 VS...

Страница 62: ...aster and Computer then click on VSI Remote button you will see the following page Selection of the remote keyboard page allows you to access any of the RegCon Pro slave on the network which control t...

Страница 63: ...displays the buffered exceptions on remote monitor starting with the oldest exception in the buffer Click the Up or Down button to move the cursor to VIEW EXCEPTIONS and click Enter Once in the except...

Страница 64: ...r will be an effor in the actual search time Verify the proper connection to the DVR from the diagram on the following page EXAMPLE Define NO SALE as an exception string In Exception No 2 HISTORY BUFF...

Страница 65: ...tilize the DVR control feature while connecting in Emulate Mode If you choose the Slave Mode this will have priority over the DVR control mode and will generate an Error Message when DVR Time Date is...

Страница 66: ...id not use shielded cable 5 May be connected to the wrong port PROBLEMS WITH ECR TPIF BOARDS 1 Upon regsiter power up verify on screen ECR power up test 2 Check that the board is seated properly in th...

Страница 67: ...o requires the input video signal to be 0 5VP P to 2V P P If the voltage is too high or low then the VSI has trouble syncing the text to the video Use an amplifier such as AVE s VDA 401 or VECA to get...

Страница 68: ...e warranty HUM BARS or NOISE IN THE VIDEO 1 Check video coax connectors for proper grounding 2 Check power ground for proper connection 3 Possible large ground loop fault and must use Video Isolation...

Страница 69: ...r alarm outputs to trigger alarming devices These are Alarm 1 2 in the Alarm menu Upon an Exception a VSI Pro can be programmed to trigger a VCR to go to its fastest record time have a Quad go full sc...

Страница 70: ...485 or RS 232 Pin 8 as an output to the DVR and only RS 232 is available from Pin 3 If you are not using the RegCom Pro in the Slave Mode then you can use RS 232 Pin 8 or RJ45 RS 485 output to the DVR...

Страница 71: ...has two RJ45 connectors on the side of the unit mainly for Network communications However only two pins of this connector is used for the networking RS 485 signals Pins 4 5 All other pins are wired i...

Страница 72: ...lied with the unit which needs to be installed on the PC prior to running the POS software The RegCom Pro can also interface with a parallel printer if a high speed parallel to serial converter is con...

Страница 73: ...to DB9 PIN 3 CTS JP5 None Not connected RTS JP4 1 2 Connect to DB9 PIN 7 Baud Rate This device can scan terminal baudrate and set device Baud rate as same as terminal Compatible Baud rate Bit per sec...

Страница 74: ...e till These interfaces output direct converted and formatted RS 232 of the printer This data can be connected directly to the AVE line of DVRs without additional conversion up to 100 If additional le...

Страница 75: ...TXD to DB9M Pin 2 JP5 CLOSE 1 2 RS 232 RXD to DB9M Pin 2 JP5 CLOSE 2 3 RS 232 RXD to DB9M Pin 3 JP6 CLOSE 1 2 Enable RS 485 JP6 CLOSE 2 3 Enable RS 422 JP7 CLOSE 1 2 Enable RS 485 JP7 CLOSE 2 3 Enabl...

Страница 76: ...ional network port for the cash register interface or any host program ming of the router or switch The TCPIP232 Adapter is not AutoSense so make sure the router is set for MDI so normal straight thru...

Страница 77: ...s using VSIs with Regcoms and a Hydra Master can simply add the RegCom Pro as a slave register interface expanding the existing system 2 Systems using the VSIs with Regcoms can replace the Hydra Maste...

Страница 78: ...y manufactures of DVR for direct storage of the transaction data on the DVR as a file rather than just inserting in the video image for recording It also supports the VSI ADD VSIAddressable format whi...

Страница 79: ...in 6 Pin 7 Pin 8 Pin 9 Figure 143 RegCom Pro Networking Connection Diagram Table 6 Hydra DB 9 Pin Out Table 7 RJ 45 Pin Out RJ 45 Pin Out Pin 1 Pin 2 Pin 3 Pin 4 RS 485 Pin 5 RS 485 Pin 6 Pin 7 Pin 8...

Страница 80: ...the Regcom and Hydra SW1 5 select the address for the Regcom and the communication parameters for the Hydra SW6 has no function SW7 has no function for the Hydra but selects Baud rate for the Regcom...

Страница 81: ...one RS 232 Com Port on the DVR The data from the Master device to the DVR Com Port has the following data format ESC ADDR TEXT TO BE DISPLAYED Where ESC is 1BH ADDR is one byte binary code The valid...

Страница 82: ...32 VSI Pro Vnetworker RS 232 or RS 422 RXD only Cash Register Networker VSI Pro RS 232 or RS 485 Full Duplex Cash Register RS 232 Hydra ASCII Data for Text Search and Exceptions RS 232 RS 232 RS 485 N...

Страница 83: ...ers The VNetHydra software is able to program the RegCom Pro or VSI Pro with Vnetworker remotely along with gather ing the transaction or exception data The VSI Pro with Networker can only send back t...

Страница 84: ...de Windows Tile Horizontally Windows Tile Vertically Windows Files C Logfiles directory contains all the files with the name extension Address1 txt Address2 txt etc corresponding to the address of the...

Страница 85: ...displayed in the VSI Pro and will be lost After a brief pause communication is established with the VSI Pro and the following menu will be displayed This is the same as the on screen menu and using t...

Страница 86: ...OFF DB9 Pin 8 Output Only one ON JP3 ON CTS Output OFF JP4 ON Network RS 232 ON Jumper Default Register RS 422 485 Termination JP2 ON Term 120 ohm OFF No Term OFF DB9 Pin 9 Selection JP6 ON 1 2 Alarm...

Страница 87: ...nd slide out the front cover 4 Remove the front cover panel completely 5 With the base cover remaining facing upward remove the remaining 4X M3 x L5mm screws 6 With the right hand thumb holding the to...

Страница 88: ...the slide reference sitting on the lower side of the top cover 11 Make sure you clear the RJ45 connectors with the top cover Assembly RegCom Pro POS Cash Register Interface 12 Press onto the base rea...

Страница 89: ...connected to read the data coming directly from an access control panel or to the server The RegCom Pro has RS 485 or RS 422 compatibility along with RS 232 in passive mode which can be con nected in...

Страница 90: ...5 Products returned without an RMA number and sales or delivery receipt showing the date of original purchase 6 Use of components that do not meet Seller s specifications 7 External parts such as cab...

Страница 91: ...ON OF THE FACT THAT SUCH PRODUCT DOES NOT CONFORM TO THE CONTRACT OR TO ANY EXPRESS OR IMPLIED WARRANTY SELLER S MAXIMUM LI ABILITY SHALL BE LIMITED TO THE COST OF REPAIR AND OR REPLACEMENT OF THE PRO...

Страница 92: ...CM24 1SJ UK Tel 440 870 770 9323 Fax 440 870 770 9363 Email ave uk multiview net www multiview net EUROPE AVE Europe LTD 123 Millennium Business Park Ballycoolin Dublin 15 Ireland Tel 353 1 684 7450...

Отзывы: