AUX-Light CAC 50Hz R410A
Trouble shooting
110
When the vertical pipe height difference is less than 5 meters, an oil loop should be installed at the bottom of
the gas (large) pipe;
When the vertical pipe height difference is more than 5 meters, then for every 5 meters an oil loop must be
installed at the bottom of the gas (large) pipe, and a short loop (liquid ring) should be installed at the exit of the
indoor unit liquid (small) pipe;
When the connecting gas pipe vertical height difference is less than 5 meters but the constant rise distance is
too long, an oil loop should be installed in the gas (large) pipe every 10 meters.
◇
When the outdoor and indoor units are at the same elevation, the oil deposit bend and liquid ring do not need
to be installed, if the horizontal connecting pipe length is less than 10 meters.
When the horizontal connecting pipe length is more than 10 metres, install an oil loop in the gas (large) pipe
every 10 metres.
Note:
This chart is for explanation purposes. An actual installation will differ from this according to the site conditions.
When making an oil trap the radius of the bend should be between 1.5 and 2 times the pipe diameter.
Содержание AL-H12/4R1D
Страница 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Страница 70: ...AUX Light CAC 50Hz R410A Universal outdoor unit 70 5 Electrical wiring and connection ALMD H18 4R1D ...
Страница 71: ...AUX Light CAC 50Hz R410A Universal outdoor unit 71 ALMD H24 4R1D ALMD H36 5R1D ALMD H48 5R1D ALMD H60 5R1D ...
Страница 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Страница 73: ...AUX Light CAC 50Hz R410A Universal outdoor unit 73 ALMD H36 4R1 ALCA H36 5R1D ALCA H48 5R1D ALCA H60 5R1D ...
Страница 91: ...AUX Light CAC 50Hz R410A Trouble shooting 91 3 Dimension AL H12 4R1D U AL H18 4R1D U AL H24 4R1D U ...
Страница 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Страница 97: ...AUX Light CAC 50Hz R410A Trouble shooting 97 AL H36 4R1 U AL H36 5R1D U AL H48 5R1D U AL H60 5R1D U ...
Страница 127: ...AUX Light CAC 50Hz R410A Trouble shooting 127 7 Failure analysis Wired controller communication failure ...
Страница 128: ...AUX Light CAC 50Hz R410A Trouble shooting 128 Communication failure between indoor and outdoor unit ...
Страница 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Страница 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Страница 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Страница 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Страница 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Страница 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Страница 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Страница 136: ...AUX Light CAC 50Hz R410A Trouble shooting 136 Refrigerant shortage or four way valve failure protection ...
Страница 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Страница 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Страница 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Страница 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Страница 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Страница 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Страница 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Страница 144: ...AUX Light CAC 50Hz R410A Trouble shooting 144 Air switch action when air conditioner starting up ...
Страница 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...