6.3 Indoor unit suspension
◇
Select the suspension foundation
◇
The suspension foundation is a structure of either wooden frame or
reinforced concrete. It must be firm and reliable to bear
at least 4 times
weight of itself and capable of bearing vibration for long periods;
Fixing of suspension foundation
◇
Fix the suspension bolts either as shown in the picture or by a steel or
wooden bracket;
◇
Adjust the relative positions of the suspension hooks to ensure the indoor
unit is level in all directions. Use a spirit level to ensure this, otherwise
water leakage, air leakage etc. will be resulted;
◇
Tighten the nuts and ensure that the hooks are tightly connected to the nuts and sMDms
, and there is no
phenomenon of virtual hanging;
◇
After the unit is installed ensure it is secure and does not shake or sway.
6.4 Drainage pipe installation
◇
The drain pipe should be properly insulated to prevent the generation of condensation
, see picture as
follows:
Heat insulation material: rubber insulation pipe with the thickness of more than 8mm
◇
Drainage pipe must have a downward gradient (1 / 50 1 / 100).If the drain pipe is installed ups and
downs, it will cause water backflow or leakage etc.
The pipe should not rise at any point.
◇
When finish installation,please carry out the drainage test to ensure that the water flow through the
pipeline fluently, and carefully observe the junction to ensure that there is no water leakage at the
junction. If the unit is installed in the newly built house, strongly recommend that this test taken before
the ceiling installation. Even it is the heating only unit, this test is unavoidable.
Содержание AL-H12/4R1D
Страница 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Страница 70: ...AUX Light CAC 50Hz R410A Universal outdoor unit 70 5 Electrical wiring and connection ALMD H18 4R1D ...
Страница 71: ...AUX Light CAC 50Hz R410A Universal outdoor unit 71 ALMD H24 4R1D ALMD H36 5R1D ALMD H48 5R1D ALMD H60 5R1D ...
Страница 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Страница 73: ...AUX Light CAC 50Hz R410A Universal outdoor unit 73 ALMD H36 4R1 ALCA H36 5R1D ALCA H48 5R1D ALCA H60 5R1D ...
Страница 91: ...AUX Light CAC 50Hz R410A Trouble shooting 91 3 Dimension AL H12 4R1D U AL H18 4R1D U AL H24 4R1D U ...
Страница 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Страница 97: ...AUX Light CAC 50Hz R410A Trouble shooting 97 AL H36 4R1 U AL H36 5R1D U AL H48 5R1D U AL H60 5R1D U ...
Страница 127: ...AUX Light CAC 50Hz R410A Trouble shooting 127 7 Failure analysis Wired controller communication failure ...
Страница 128: ...AUX Light CAC 50Hz R410A Trouble shooting 128 Communication failure between indoor and outdoor unit ...
Страница 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Страница 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Страница 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Страница 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Страница 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Страница 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Страница 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Страница 136: ...AUX Light CAC 50Hz R410A Trouble shooting 136 Refrigerant shortage or four way valve failure protection ...
Страница 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Страница 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Страница 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Страница 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Страница 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Страница 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Страница 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Страница 144: ...AUX Light CAC 50Hz R410A Trouble shooting 144 Air switch action when air conditioner starting up ...
Страница 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...