AUX-Light CAC 50Hz R410A
Universal outdoor unit
79
7.6 Drainage pipe
◇
Drainage pipes must be wrapped with heat insulation materials, otherwise it will cause frost or
droplets, see picture as follows:
Heat insulation material: rubber insulation pipe with the thickness of more than 8mm
◇
Drainage pipe must have a downward gradient (1 / 50 1 / 100).If the drain pipe is installed ups and
downs, it will cause water backflow or leakage etc.
◇
When finish installation please carry out the drainage test to ensure that the water flow through the
pipeline fluently, and carefully observe the junction to ensure that there is no water leakage at the
junction. If the unit is installed in the newly built house, strongly recommend that this test taken before
the CFiling installation. Even it is the heating only unit, this test is unavoidable.
7.7 Remote controller receiver
◇
Installation site: recommend that the receiver is mounted with the distance of 30~50 cm to the
indoor unit air outlet(on your choice as well), while must ensure that the receiver can get the
signal that the remote controller sends, please refer to the following installation picture:
◇
Mounting hole set up: please use certain instrument to dig a square hole with 88*88mm on the ceiling
◇
Remote controller receiver installation.
Hold the two sides (with clip sides) of the receiver, set the spring clip in the vertical way then put it into
the mounting hole, if the two sides of the receiver is in the same level with the ceiling the installation
is finished.
◇
Signal line connection: connect the wire of remote controller receiver to the CN-DISP terminal board
on PCB of indoor unit wire box then fix it.
Содержание AL-H12/4R1D
Страница 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Страница 70: ...AUX Light CAC 50Hz R410A Universal outdoor unit 70 5 Electrical wiring and connection ALMD H18 4R1D ...
Страница 71: ...AUX Light CAC 50Hz R410A Universal outdoor unit 71 ALMD H24 4R1D ALMD H36 5R1D ALMD H48 5R1D ALMD H60 5R1D ...
Страница 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Страница 73: ...AUX Light CAC 50Hz R410A Universal outdoor unit 73 ALMD H36 4R1 ALCA H36 5R1D ALCA H48 5R1D ALCA H60 5R1D ...
Страница 91: ...AUX Light CAC 50Hz R410A Trouble shooting 91 3 Dimension AL H12 4R1D U AL H18 4R1D U AL H24 4R1D U ...
Страница 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Страница 97: ...AUX Light CAC 50Hz R410A Trouble shooting 97 AL H36 4R1 U AL H36 5R1D U AL H48 5R1D U AL H60 5R1D U ...
Страница 127: ...AUX Light CAC 50Hz R410A Trouble shooting 127 7 Failure analysis Wired controller communication failure ...
Страница 128: ...AUX Light CAC 50Hz R410A Trouble shooting 128 Communication failure between indoor and outdoor unit ...
Страница 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Страница 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Страница 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Страница 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Страница 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Страница 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Страница 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Страница 136: ...AUX Light CAC 50Hz R410A Trouble shooting 136 Refrigerant shortage or four way valve failure protection ...
Страница 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Страница 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Страница 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Страница 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Страница 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Страница 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Страница 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Страница 144: ...AUX Light CAC 50Hz R410A Trouble shooting 144 Air switch action when air conditioner starting up ...
Страница 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...