Trouble shooting
106
Piping connection
◇
Using expanding machine to expand accessories, the size of horn shown in the above figure:
◇
Paint a thin layer of frozen oil at both inside and outside part of the expanding.
◇
Make the expanding right to the screw thread shape connection of the indoor unit, using hands to
tighten the nut then using a wrench to tighten the nut again, the tighten torque as follows figure.
◇
Take out the cover of the indoor unit gas valve and liquid valve, make the expanding right to the stop
valve of outdoor unit, using hands to tighten the nut then using a wrench to tighten the nut again, the
tighten torque as follows figure.
Equivalent pipe length conversion
Equivalent pipe length meansconverting pipe elbow to straight pipe length after considerate the pressure
loss.
Elbow and Oil loop conversion tablet
Pipe Dia.(mm)
Bend
Oil Loop
6.35
0.10
0.7
9.52
0.18
1.3
12.70
0.20
1.5
15.88
0.25
2.0
19.05
0.35
2.4
22.02
0.40
3.0
Equivalent pipe length L
=
ActualPipe length L+ Bend Qty× Equivalent pipe bend Oil Loop Qty ×
Equivalent Oil Loop length
Sample:
ALCA-H42A
5/C5 Actual Pipe length is 25 meters, Gas pipe diameter is 19.05mm. If there’s 5 bends and 2
oil loops during the installation, then the equivalent pipe length should be:
L=25+0.35×5+2.4×2=31.5(m)
◇
Specification of connection pipe for indoor unit and outdoor unit
Cooling Capacity(Btu/h)
12000
18000
24000
36000
48000
60000
Connection
Pipe (mm)
Liquid Pipe
Φ6.35
Φ9.52
Φ9.52
Gas Pipe
Φ12.7
Φ15.88
Φ19.05
Max. Length
15
20
30
50
50
Max. Height (m)
10
15
15
30
30
Содержание AL-H12/4R1D
Страница 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Страница 70: ...AUX Light CAC 50Hz R410A Universal outdoor unit 70 5 Electrical wiring and connection ALMD H18 4R1D ...
Страница 71: ...AUX Light CAC 50Hz R410A Universal outdoor unit 71 ALMD H24 4R1D ALMD H36 5R1D ALMD H48 5R1D ALMD H60 5R1D ...
Страница 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Страница 73: ...AUX Light CAC 50Hz R410A Universal outdoor unit 73 ALMD H36 4R1 ALCA H36 5R1D ALCA H48 5R1D ALCA H60 5R1D ...
Страница 91: ...AUX Light CAC 50Hz R410A Trouble shooting 91 3 Dimension AL H12 4R1D U AL H18 4R1D U AL H24 4R1D U ...
Страница 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Страница 97: ...AUX Light CAC 50Hz R410A Trouble shooting 97 AL H36 4R1 U AL H36 5R1D U AL H48 5R1D U AL H60 5R1D U ...
Страница 127: ...AUX Light CAC 50Hz R410A Trouble shooting 127 7 Failure analysis Wired controller communication failure ...
Страница 128: ...AUX Light CAC 50Hz R410A Trouble shooting 128 Communication failure between indoor and outdoor unit ...
Страница 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Страница 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Страница 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Страница 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Страница 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Страница 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Страница 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Страница 136: ...AUX Light CAC 50Hz R410A Trouble shooting 136 Refrigerant shortage or four way valve failure protection ...
Страница 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Страница 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Страница 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Страница 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Страница 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Страница 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Страница 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Страница 144: ...AUX Light CAC 50Hz R410A Trouble shooting 144 Air switch action when air conditioner starting up ...
Страница 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...