Enabling
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 84
12.3 Enabling Activated / Deactivated Components
Setting the arm state of a disabled
deactivated
component to
ENABLED will have no immediate effect on system operation. The
component will remain deactivated until its activation state is set to an
active state (on alarm or on command).
12.4 Enabling Detection Zones
When you enable a
Detection Zone
- all points within the specified
detection zone will be enabled - except for those that are individually
disabled as described in the subsequent chapter. A detection zone will
not be indicated as enabled unless
at least one point
within the zone
is enabled.
12.5 Enabling Points
When a
Point
(fire detectors / manual call-points) is enabled (manually
or when the disablement time expires), alarm signals will be sent from
this point in the event of an alarm.
If
all
points in a detection zone are disabled, the detection zone will be
indicated as disabled. If at least one point within this detection zone is
enabled, the detection zone will be indicated as enabled. If the points
are given different disablement times, the detection zone will be
automatically
indicated as enabled when the
first
point is enabled (i.e.
when the point with the shortest disablement time is enabled).
12.6 Enabling Fire Alarm Devices
When you enable a
Fire Alarm Device (FAD)
, the output which
controls the FAD will be enabled. The FAD will now give an audible
indication.
You can enable a single unit (FAD) / alarm circuit, or all units (FADs)
in a selected Alarm Zone.