Panel Overview
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 19
2.7.3 The Operator Section (lower right section)
Applies to operator panels BS-420 / BS-430.
MultiS SmokeDis
The MultiSensor provides both smoke and heat detection. The smoke detection can be disabled, thus
only heat detection is present. The indicator has the following behaviour:
Steady yellow light:
The smoke detection is disabled.
Dual Safety Stdby
Applicable to systems using the Dual Safety concept; a system with redundant loop control consisting
of a Primary and Secondary System.
Steady yellow light:
The panel is in
Standby Mode
, i.e. this panel does not control the detection loops. The panel(s) in
the other system controls the detection loops and is in
Active Mode.
Blinking light: the panel does not control all detection loops/loop units, and/or loop control is being
transferred
Active Sensors
The Active Sensors LED applies to configurations with fan control functionality.
Steady yellow light.
At least one Smoke Sensor detects smoke.