CONe OF vISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
See Figure 18.
ReSPONSe TIMe—
32 inch methane plume: < 10 seconds.
1 foot x 1 foot n-Heptane: < 15 seconds.
(See Appendix A for details.)
eNCLOSuRe MATeRIAL—
Copper-free aluminum (painted) or 316 stainless steel.
vIbRATION—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).
DIMeNSIONS—
See Figure 19.
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm
2
wire.
Screw terminal required torque range is 3.5–4.4 in.-lbs.
(0.4-0.5 N·m).
14 AWG (2.08 mm
2
) or 16 AWG (1.31 mm
2
) shielded
cable is recommended.
Important:
18 Vdc minimum must be available at the
detector. For ambient temperatures below –10°C and
above +60°C use field wiring suitable for both minimum
and maximum ambient temperature.
THReAD SIZe—
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.
SHIPPING WeIGHT (Approximate)—
Aluminum:
6 pounds (2.75 kilograms).
Stainless Steel: 10 pounds (4.5 kilograms).
Swivel Mount (AL): 6 pounds (2.75 kilograms).
Swivel Mount (SS): 14 pounds (6.4 kilograms).
WARRANTY PeRIOD—
3 years.
CeRTIFICATION—
FM
APPROVED
®
VdS
For complete approval details, refer to the appropriate
Appendix:
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX/CE
Appendix D - IECEx
Appendix E - VdS.
0
∞
15
∞
30
∞
45
∞
15
∞
30
∞
45
∞
VIEWING ANGLE
A1288
100
90
80
70
60
50
40
30
20
10
DETECTION
DISTANCE
(PERCENT)
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
INCIDENCE DECREASES.
Figure 18—Detector Cone of vision
10.2
(25.9)
4.8
(12.2)
4.7
(11.9)
B2223
Figure 19—Dimensions in Inches (cm)
Instructions, AutroFlame X98AF 116-P-X98AF/IGB, Rev. D, 2012-02-02, Autronica Fire and Security AS
95-8683, Rev: 8/11
Page
20