REPlaCEmENT PaRTS

The detector is not designed to be repaired in the field.  

If a problem should develop, refer to the Troubleshooting 

section.  If it is determined that the problem is caused by 

an electronic defect, the device must be returned to the 

factory for repair.  

DEVICE REPaIR aND RETURN

Prior  to  returning  devices,  contact  the  nearest  local 

Detector  Electronics  office  so  that  a  Return  Material 

Identification  (RMI)  number  can  be  assigned.   

written  statement  describing  the  malfunction  must 
accompany  the  returned  device  or  component  to 
assist  and  expedite  finding  the  root  cause  of  the 
failure.

Pack  the  unit  properly.    Always  use  sufficient  packing 

material.    Where  applicable,  use  an  antistatic  bag  as 

protection from electrostatic discharge.

NOTE

Det-Tronics  reserves  the  right  to  apply  a  service 
charge for repairing returned product damaged as 
a result of improper packaging.

Return all equipment transportation prepaid to the factory 

in Minneapolis.

NOTE 

It  is  highly  recommended  that  a  complete  spare 
be  kept  on  hand  for  field  replacement  to  ensure 
continuous protection. 

ORDERINg INfORmaTION

When ordering, please specify:
X98AF IR Flame Detector
Refer to the X98AF Model Matrix below for details
Q9033 mount is required:

Q9033A for aluminum detectors only.

Q9033B for aluminum and stainless steel detectors.

X-sERIEs FLAME DETECTOR ACCEssORIEs

part Number

Description

116-000511-029

Converter RS485 to RS232

116-007819-001

W6300B1002 Serial Inspector Connector

 (Inspector Monitor software included)

116-007819-002

W6300B1003 USB Inspector Connector

 (Inspector Monitor software included)

116-009207-001

Flame Inspector Monitor CD

116-103922-001

Model 475 HART Communicator

116-102740-002

Magnet

116-007739-001

Magnet and Extension Pole

116-009208-001

oi

 Replacement kit for X3301 (5 Black reflector plates) 

with Inspector Connector and Monitor

116-010831-001

oi

 Replacement kit for X3301 (5 Stainless Steel reflector plates) 

with Inspector Connector and Monitor

116 009208-003

oi

 Replacement kit for X3302 (5 Black reflector plates) 

with Inspector Connector and Monitor

116 010831-002

oi

 Replacement kit for X3302 (5 Stainless Steel reflector plates) 

with Inspector Connector and Monitor

116-009208-002

oi

 Replacement kit for X52/X22/X98 (5 reflector plates) 

with Inspector Connector and Monitor

116 007307-001

Replacement 

oi

 reflector plate for X3301 with Black plate 

(requires inspector connector to calibrate)

116 010830-001

Replacement 

oi

 reflector plate for X3301 with Stainless Steel 

plate (requires inspector connector to calibrate)

116 007307-003

Replacement 

oi

 reflector plate for X3302 with Black plate 

(requires inspector connector to calibrate)

116 010830-002

Replacement 

oi

 reflector plate for X3302 with Stainless Steel 

plate (requires inspector connector to calibrate)

116-007307-002

Replacement 

oi

 reflector plate for X52/X22/X98 

(requires inspector connector to calibrate)

116-007240-001

Q1116A1001, Air Shield (AL)

116-007818-001

Q1118A1001 Aluminum Air Shield/Flange Mount (AL)

116-007818-002

Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)

116-009177-001

Q1120A1001 Paint shield mounting ring (AL)

116-009199-001

Q1198A1001 Dual Air Shield/Flange Mount (X98AF only)/(AL)

116-006097-001

Q1201 Laser

116-102871-001

Laser Battery, 3V Lithium (laser)

116-007255-001

Q1201C1001 X-Series Laser Holder (AL/Plastic)

116-007338-001

Q2000A1001 X-Series Weather Shield (AL)

116 007338-010

Q2033A10R X3301/X3302 FOV Limiter 10° (AL)

116 007338-020

Q2033A20R X3301/X3302 FOV Limiter 20° (AL)

116 007338-030

Q2033A30R X3301/X3302 FOV Limiter 30° (AL)

116 007912-010

Spare Restrictor Plate 10° (AL)

116 007912-020

Spare Restrictor Plate 20° (AL)

116 007912-030

Spare Restrictor Plate 30° (AL)

116-007290-001

Q9033B Stainless Steel Swivel Mount Assembly is for 

aluminum and stainless steel detectors

116-007290-002

Q9033A Aluminum Swivel Mount Assembly is for aluminum 

detectors only 

116-101197-003

Stop Plug, SS, IP66, Ex d e, M25 (SS)

116-103517-001

Stop Plug, AL, IP66, Ex d e, M25 (AL)

116-103363-001

14 mm Hex Wrench (Steel)

116-103406-001

Screwdriver

116-107427-040

O-ring - Rear Cover (Viton)

116-005003-001

1 oz grease for detectors (non-silicon)

116-001680-001

Window cleaner (6 pack)

Instructions, AutroFlame X98AF 116-P-X98AF/IGB, Rev. D, 2012-02-02, Autronica Fire and Security AS

95-8683, Rev: 8/11

Page 

21

Содержание AutroFlame X98AF

Страница 1: ...Instructions AutroFlame X98AF IR Flame Detector Instructions AutroFlame X98AF 116 P X98AF IGB Rev D 2012 02 02 Autronica Fire and Security AS 95 8683 Rev 8 11 ...

Страница 2: ...sibility for any errors that may appear in the publication or for damages arising from the information in it No information in this publication should be regarded as a warranty made by Autronica Fire and Security The information in this publication may be updated without notice Product names mentioned in this publication may be trademarks They are used only for identification ...

Страница 3: ...ion 9 Detector Positioning 9 Detector Orientation 9 Protection Against Moisture Damage 9 Wiring Procedure 10 EOL Resistors 11 Startup Procedure 17 Fire Alarm Test 17 Troubleshooting 17 Maintenance 17 Cleaning Procedure 18 oi Plate Removal 18 Periodic Checkout Procedure 18 Clock Battery 18 Features 19 Specifications 19 Replacement Parts 21 Device Repair And Return 21 Ordering Information 21 Accesso...

Страница 4: ...put configuration includes fire fault and auxiliary relays Output options include 0 to 20 mA output in addition to the three relays Pulse output for compatibility with existing controller based systems with fire and fault relays HART Communication A tricolor LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions Microprocessor controlled h...

Страница 5: ... to verify complete detector operation capabilities No testing with an external test lamp is required The detector automatically performs the same test that a maintenance person with a test lamp would perform once every minute 60 times per hour However a successful automatic oi test does not produce an alarm condition The X98AF signals a fault condition when less than half of the detection range r...

Страница 6: ...gain when the status changes Data is accessible using the RS 485 port integral wiring compartment All external wiring to the device is connected within the integral junction box The screw terminals accept wiring from 14 to 24 AWG The detector is furnished with four conduit entries with either 3 4 inch NPT or 25 mm threads Signal Processing options The X98AF features signal processing options These...

Страница 7: ...nt to interference by EMI and RFI and is EMC Directive compliant and CE marked It will not respond to a 5 watt walkie talkie at distances greater than 1 foot Non Carbon Fires The response of the X98AF is limited to carbonaceous fuels It should not be used to detect fires from fuels that do not contain carbon such as hydrogen sulfur and burning metals FALSE ALARM SOURCES The detector has been desig...

Страница 8: ...afETY NOTES WarnIng Do not open the detector assembly in a hazardous area when power is applied The detector contains limited serviceable components and should never be opened Doing so could disturb critical optical alignment and calibration parameters possibly causing serious damage This type of damage could be undetected and could result in failure to see a fire and or false alarm CaUtIon The wi...

Страница 9: ...he system are properly aimed at the area to be protected The Det Tronics Q1201C Laser Aimer is recommended for this purpose If possible fire tests should be conducted to verify correct detector positioning and coverage For ATEX installations the X98AF detector housing must be electrically connected to earth ground detector Orientation Refer to Figure 2 and ensure that the oi plate will be oriented...

Страница 10: ... minimum input voltage of 18 Vdc must be present at the X98AF note Refer to Power Consumption in the Specifications section of this manual The use of shielded cable is required to protect against interference caused by EMI and RFI When using cables with shields terminate the shields as shown in Figures 7 through 12 and Figure 14 Consult the factory if not using shielded cable In applications where...

Страница 11: ...pation not to exceed 2 5 watts This applies to ATEX IEC installations only 2 Resistor leads should be cut to a length of approximately 1 1 2 inches 40 mm 3 Bend the leads and install the EOL resistor as shown in Figure 6 4 Maintain a 3 8 inch 10 mm minimum gap between the resistor body and the terminal block or any other neighboring parts NOTE The EOL resistor can only be used within the flameproo...

Страница 12: ...20 mA REF 4 20 mA REF COM AUX N O AUX N C AUX Figure 7 Ex d Wiring Option B2177 FIRE ALARM PANEL X9800 DETECTOR ALARM ALARM 24 VDC WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN N O AND COMMON COM CONTACTS ARE CLOSED 2 ALARM RELAY IS NORMALLY DE ENERGIZED WITH NO ALARM CONDITION PRESENT 3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE...

Страница 13: ...EST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 24 VDC 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 MAN Oi X9800 DETECTOR 24 VDC Figure 11 X98AF Detector Wired for Isolated 0 to 20 mA Current Output Sourcing 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC C2181 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 24 VDC 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 MAN Oi X9800...

Страница 14: ...EST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 MAN Oi X98 DETECTOR 24 VDC Figure 11 AutroFlame X98AF Detector Wired for Isolated 0 to 20 mA Current Output Sourcing 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC C2181 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 MAN Oi X98 DETECT...

Страница 15: ... MAN Oi 4 20 mA 4 20 mA 4 20 mA REF 4 20 mA REF COM AUX N O AUX N C AUX EOL 1K5 620 OHM 24V DC Figure 13 EEx d wiring option AutroSafe Figure 14 EEx e wiring option AutroSafe C NC NO 11 10 9 8 7 6 5 2K BN 320 1 2 3 4 Detector loop in Detector loop out Detector loop out Detector loop in DETECTOR EEx d wiring WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING THE FAULT RELAY COIL IS ENERGIZ...

Страница 16: ...C 1 2 3 4 5 6 Detector loop in Detector loop out Detector loop out Detector loop in BN 300 Figure 15 EEx d wiring option AutroSafe non latching detector Figure 16 EEx e wiring option AutroSafe non latching detector 1 2 3 4 5 6 BN 300 Detector loop in Detector loop out Detector loop out Detector loop in DETECTOR EEx d wiring non latching detector WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OC...

Страница 17: ...nnect wiring at the detector before checking system wiring for continuity 6 If all wiring checks out and cleaning of the oi plate window did not correct the fault condition check for high levels of background IR radiation by covering the detector with the factory supplied cover or aluminum foil If the fault condition clears extreme background IR radiation is present Re adjust the view of the detec...

Страница 18: ...s and the need for oi plate replacement oi plate Removal and replacement 1 Disable any extinguishing equipment that is connected to the unit 2 Loosen the two captive screws then grasp the oi plate by the visor and remove it from the detector See Figure 17 3 Install the new or cleaned oi plate 4 Re calibrate the detector s oi system Caution Do not replace the oi reflector plate without also recalib...

Страница 19: ...atts at 30 Vdc in alarm Heater only 8 watts maximum Total power 16 5 watts at 30 Vdc with EOL resistor installed and heater on maximum EOL resistor must be ceramic wirewound type rated 5 watts minimum with actual power dissipation not to exceed 2 5 watts For HART model refer to Addendum number 95 8637 POWER UP TIME Fault indication clears after 0 5 second device is ready to indicate an alarm condi...

Страница 20: ...ing suitable for both minimum and maximum ambient temperature Thread SIZE Conduit connection Four entries 3 4 inch NPT or M25 Conduit seal not required SHIPPING WEIGHT Approximate Aluminum 6 pounds 2 75 kilograms Stainless Steel 10 pounds 4 5 kilograms Swivel Mount AL 6 pounds 2 75 kilograms Swivel Mount SS 14 pounds 6 4 kilograms WARRANTY PERIOD 3 years CERTIFICATION FM APPROVED VdS For complete ...

Страница 21: ... with Inspector Connector and Monitor 116 010831 002 oi Replacement kit for X3302 5 Stainless Steel reflector plates with Inspector Connector and Monitor 116 009208 002 oi Replacement kit for X52 X22 X98 5 reflector plates with Inspector Connector and Monitor 116 007307 001 Replacement oi reflector plate for X3301 with Black plate requires inspector connector to calibrate 116 010830 001 Replacemen...

Страница 22: ...OUTPUTS 11 Relay 13 Relay and 4 20 mA 15 Relay and Pulse 16 Addressable Module Only Third Party Type 23 HART Relay and 4 20 mA TYPE APPROVAL AGENCY W FM CSA ATEX CE IECEx TYPE CLASSIFICATION 1 Division Zone Ex d e 2 Division Zone Ex d Detectors are always Class I Div 1 Instructions AutroFlame X98AF 116 P X98AF IGB Rev D 2012 02 02 Autronica Fire and Security AS 95 8683 Rev 8 11 Page 22 ...

Страница 23: ...ce of contamination on any single or combination of lens surfaces resulting in a loss of approximately 50 of its detection range verifying that the detector performs a calibrated Automatic Optical Integrity oi test for each sensor Upon removal of the contamination the detector fault was cleared and the detector was verified to detect a fire MANUAL OPTICAL INTEGRITY TEST The Manual Magnetic oi perf...

Страница 24: ...ch dia Heptane 10 3 30 Sunlight reflected modulated unmodulated 2 inch dia Heptane 10 3 30 70 w sodium vapor lamp unmodulated 5 1 5 2 inch dia Heptane 5 1 5 3 70 w sodium vapor lamp modulated 5 1 5 2 inch dia Heptane 5 1 5 3 250 w mercury vapor lamp unmodulated 5 1 5 2 inch dia Heptane 5 1 5 2 250 w mercury vapor lamp modulated 5 1 5 2 inch dia Heptane 5 1 5 3 300 w incandescent lamp unmodulated 5...

Страница 25: ...istance feet m Horizontal degrees Typical Horiz Response Time seconds Vertical degrees Typical Vert Response Time seconds Black Powder 40 Grams 5 1 5 45 45 0 04 0 03 45 30 0 04 0 04 FALSE ALARM IMMUNITY High Sensitivity TDSA On Quick Fire Off False Alarm Souce Distance feet m Modulated Response Unmodulated Response Sunlight direct reflected No alarm No alarm Vibration NA No alarm No alarm Arc weld...

Страница 26: ...s E F and G T5 Class I Division 2 Groups A B C and D T3 Class II Division 2 Groups F and G T3 Class III Enclosure Type 4X Infrared Flame Detector Controller X98AF series rated 18 30 Vdc 2 1 Watts to 16 5 Watts Relay contacts rated 5 Amps 30 Vdc Instructions AutroFlame X98AF 116 P X98AF IGB Rev D 2012 02 02 Autronica Fire and Security AS 95 8683 Rev 8 11 Page 26 ...

Страница 27: ...artment in type of explosion protection flameproof enclosure d or in type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The metal housing for the Infrared IR...

Страница 28: ...nts shall be certified to E generation or ATEX standards in type of explosion protection increased safety e or flameproof enclosure d as applicable suitable for the conditions of use and correctly installed They shall maintain the degree of ingress protection IP66 for the apparatus Unused apertures shall be closed with suitable blanking elements Note For ATEX installations the X98AF detector housi...

Страница 29: ... explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The metal housing for the Infrared IR flame detector type X98AF must be electrically connected to earth ground Fo...

Страница 30: ...Fire Detection and Fire Alarm Systems BASIS OF APPROVAL DIN EN 54 Part 10 05 02 Flame Detectors Instructions for the application of the approval component system The installation shall take into account that the orientation arrow on the flame detector is directed upwards as the view angle in this direction is 90 The IR flame detector corresponds to class 1 Instructions AutroFlame X98AF 116 P X98AF...