FACTORs INHIbITING DETECTOR REspONsE

windows

Glass  and  Plexiglas  windows  signifi cantly  attenuate 

radiation and must not be located between the detector 

and a potential fl ame source.  If the window cannot be 

eliminated  or  the  detector  location  changed,  contact 

Detector  Electronics  Corporation's  (Det-Tronics®)  for 

recommendations  regarding  window  materials  that  will 

not attenuate radiation.

Obstructions

Radiation  must  be  able  to  reach  the  detector  in  order 

for it to respond.  Care must be taken to keep physical 

obstructions out of the line of view of the detector.

smoke

Smoke  will  absorb  radiation.    If  accumulations  of  dense 

smoke can be expected to precede the presence of a fl ame, 

then detectors that are used in enclosed areas should be 

mounted on the wall approximately 3 feet (1 meter) from the 

ceiling where the accumulation of smoke is reduced.

Detector viewing windows

It is important to keep the detector viewing windows as 

free  of  contaminants  as  possible  in  order  to  maintain 

maximum sensitivity.  Commonly encountered substances 

that can signifi cantly attenuate IR radiation include, but 

are certainly not limited to, the following:
Dust and dirt buildup

Paint overspray

Water and ice.

ImPORTaNT SafETY NOTES

WarnIng

Do not open the detector assembly in a hazardous 

area when power is applied.  The detector contains 

limited serviceable components and should never 

be opened.  Doing so could disturb critical optical 

alignment  and  calibration  parameters,  possibly 

causing  serious  damage.   This  type  of  damage 

could be undetected and could result in failure to 

see a fi re and/or false alarm.

CaUtIon

The wiring procedures in this manual are intended 

to  ensure  proper  functioning  of  the  device  under 

normal  conditions.    However,  because  of  the 

many  variations  in  wiring  codes  and  regulations, 

total  compliance  to  these  ordinances  cannot  be 

guaranteed.    Be  certain  that  all  wiring  complies 

with  the  NEC  as  well  as  all  local  ordinances.    If 

in  doubt,  consult  the  authority  having  jurisdiction 

before  wiring  the  system.    Installation  must  be 

done by a properly trained person.

CaUtIon

To  prevent  unwanted  actuation  or  alarm, 

extinguishing  devices  must  be  disabled  prior  to 

performing detection system tests or maintenance.

CaUtIon

The IR fl ame detectors are to be installed in places 
where the risk of mechanical damages is low.

attEntIon

Remove  the  protective  cap  from  the  front  of  the 

detector before activating the system.

attEntIon

Observe  precautions  for  handling  electrostatic 

sensitive devices.

Instructions, AutroFlame X98AF 116-P-X98AF/IGB, Rev. D, 2012-02-02, Autronica Fire and Security AS

95-8683, Rev: 8/11

Page 

8

Содержание AutroFlame X98AF

Страница 1: ...Instructions AutroFlame X98AF IR Flame Detector Instructions AutroFlame X98AF 116 P X98AF IGB Rev D 2012 02 02 Autronica Fire and Security AS 95 8683 Rev 8 11 ...

Страница 2: ...sibility for any errors that may appear in the publication or for damages arising from the information in it No information in this publication should be regarded as a warranty made by Autronica Fire and Security The information in this publication may be updated without notice Product names mentioned in this publication may be trademarks They are used only for identification ...

Страница 3: ...ion 9 Detector Positioning 9 Detector Orientation 9 Protection Against Moisture Damage 9 Wiring Procedure 10 EOL Resistors 11 Startup Procedure 17 Fire Alarm Test 17 Troubleshooting 17 Maintenance 17 Cleaning Procedure 18 oi Plate Removal 18 Periodic Checkout Procedure 18 Clock Battery 18 Features 19 Specifications 19 Replacement Parts 21 Device Repair And Return 21 Ordering Information 21 Accesso...

Страница 4: ...put configuration includes fire fault and auxiliary relays Output options include 0 to 20 mA output in addition to the three relays Pulse output for compatibility with existing controller based systems with fire and fault relays HART Communication A tricolor LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions Microprocessor controlled h...

Страница 5: ... to verify complete detector operation capabilities No testing with an external test lamp is required The detector automatically performs the same test that a maintenance person with a test lamp would perform once every minute 60 times per hour However a successful automatic oi test does not produce an alarm condition The X98AF signals a fault condition when less than half of the detection range r...

Страница 6: ...gain when the status changes Data is accessible using the RS 485 port integral wiring compartment All external wiring to the device is connected within the integral junction box The screw terminals accept wiring from 14 to 24 AWG The detector is furnished with four conduit entries with either 3 4 inch NPT or 25 mm threads Signal Processing options The X98AF features signal processing options These...

Страница 7: ...nt to interference by EMI and RFI and is EMC Directive compliant and CE marked It will not respond to a 5 watt walkie talkie at distances greater than 1 foot Non Carbon Fires The response of the X98AF is limited to carbonaceous fuels It should not be used to detect fires from fuels that do not contain carbon such as hydrogen sulfur and burning metals FALSE ALARM SOURCES The detector has been desig...

Страница 8: ...afETY NOTES WarnIng Do not open the detector assembly in a hazardous area when power is applied The detector contains limited serviceable components and should never be opened Doing so could disturb critical optical alignment and calibration parameters possibly causing serious damage This type of damage could be undetected and could result in failure to see a fire and or false alarm CaUtIon The wi...

Страница 9: ...he system are properly aimed at the area to be protected The Det Tronics Q1201C Laser Aimer is recommended for this purpose If possible fire tests should be conducted to verify correct detector positioning and coverage For ATEX installations the X98AF detector housing must be electrically connected to earth ground detector Orientation Refer to Figure 2 and ensure that the oi plate will be oriented...

Страница 10: ... minimum input voltage of 18 Vdc must be present at the X98AF note Refer to Power Consumption in the Specifications section of this manual The use of shielded cable is required to protect against interference caused by EMI and RFI When using cables with shields terminate the shields as shown in Figures 7 through 12 and Figure 14 Consult the factory if not using shielded cable In applications where...

Страница 11: ...pation not to exceed 2 5 watts This applies to ATEX IEC installations only 2 Resistor leads should be cut to a length of approximately 1 1 2 inches 40 mm 3 Bend the leads and install the EOL resistor as shown in Figure 6 4 Maintain a 3 8 inch 10 mm minimum gap between the resistor body and the terminal block or any other neighboring parts NOTE The EOL resistor can only be used within the flameproo...

Страница 12: ...20 mA REF 4 20 mA REF COM AUX N O AUX N C AUX Figure 7 Ex d Wiring Option B2177 FIRE ALARM PANEL X9800 DETECTOR ALARM ALARM 24 VDC WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN N O AND COMMON COM CONTACTS ARE CLOSED 2 ALARM RELAY IS NORMALLY DE ENERGIZED WITH NO ALARM CONDITION PRESENT 3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE...

Страница 13: ...EST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 24 VDC 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 MAN Oi X9800 DETECTOR 24 VDC Figure 11 X98AF Detector Wired for Isolated 0 to 20 mA Current Output Sourcing 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC C2181 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 24 VDC 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 MAN Oi X9800...

Страница 14: ...EST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 MAN Oi X98 DETECTOR 24 VDC Figure 11 AutroFlame X98AF Detector Wired for Isolated 0 to 20 mA Current Output Sourcing 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC C2181 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 MAN Oi X98 DETECT...

Страница 15: ... MAN Oi 4 20 mA 4 20 mA 4 20 mA REF 4 20 mA REF COM AUX N O AUX N C AUX EOL 1K5 620 OHM 24V DC Figure 13 EEx d wiring option AutroSafe Figure 14 EEx e wiring option AutroSafe C NC NO 11 10 9 8 7 6 5 2K BN 320 1 2 3 4 Detector loop in Detector loop out Detector loop out Detector loop in DETECTOR EEx d wiring WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING THE FAULT RELAY COIL IS ENERGIZ...

Страница 16: ...C 1 2 3 4 5 6 Detector loop in Detector loop out Detector loop out Detector loop in BN 300 Figure 15 EEx d wiring option AutroSafe non latching detector Figure 16 EEx e wiring option AutroSafe non latching detector 1 2 3 4 5 6 BN 300 Detector loop in Detector loop out Detector loop out Detector loop in DETECTOR EEx d wiring non latching detector WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OC...

Страница 17: ...nnect wiring at the detector before checking system wiring for continuity 6 If all wiring checks out and cleaning of the oi plate window did not correct the fault condition check for high levels of background IR radiation by covering the detector with the factory supplied cover or aluminum foil If the fault condition clears extreme background IR radiation is present Re adjust the view of the detec...

Страница 18: ...s and the need for oi plate replacement oi plate Removal and replacement 1 Disable any extinguishing equipment that is connected to the unit 2 Loosen the two captive screws then grasp the oi plate by the visor and remove it from the detector See Figure 17 3 Install the new or cleaned oi plate 4 Re calibrate the detector s oi system Caution Do not replace the oi reflector plate without also recalib...

Страница 19: ...atts at 30 Vdc in alarm Heater only 8 watts maximum Total power 16 5 watts at 30 Vdc with EOL resistor installed and heater on maximum EOL resistor must be ceramic wirewound type rated 5 watts minimum with actual power dissipation not to exceed 2 5 watts For HART model refer to Addendum number 95 8637 POWER UP TIME Fault indication clears after 0 5 second device is ready to indicate an alarm condi...

Страница 20: ...ing suitable for both minimum and maximum ambient temperature Thread SIZE Conduit connection Four entries 3 4 inch NPT or M25 Conduit seal not required SHIPPING WEIGHT Approximate Aluminum 6 pounds 2 75 kilograms Stainless Steel 10 pounds 4 5 kilograms Swivel Mount AL 6 pounds 2 75 kilograms Swivel Mount SS 14 pounds 6 4 kilograms WARRANTY PERIOD 3 years CERTIFICATION FM APPROVED VdS For complete ...

Страница 21: ... with Inspector Connector and Monitor 116 010831 002 oi Replacement kit for X3302 5 Stainless Steel reflector plates with Inspector Connector and Monitor 116 009208 002 oi Replacement kit for X52 X22 X98 5 reflector plates with Inspector Connector and Monitor 116 007307 001 Replacement oi reflector plate for X3301 with Black plate requires inspector connector to calibrate 116 010830 001 Replacemen...

Страница 22: ...OUTPUTS 11 Relay 13 Relay and 4 20 mA 15 Relay and Pulse 16 Addressable Module Only Third Party Type 23 HART Relay and 4 20 mA TYPE APPROVAL AGENCY W FM CSA ATEX CE IECEx TYPE CLASSIFICATION 1 Division Zone Ex d e 2 Division Zone Ex d Detectors are always Class I Div 1 Instructions AutroFlame X98AF 116 P X98AF IGB Rev D 2012 02 02 Autronica Fire and Security AS 95 8683 Rev 8 11 Page 22 ...

Страница 23: ...ce of contamination on any single or combination of lens surfaces resulting in a loss of approximately 50 of its detection range verifying that the detector performs a calibrated Automatic Optical Integrity oi test for each sensor Upon removal of the contamination the detector fault was cleared and the detector was verified to detect a fire MANUAL OPTICAL INTEGRITY TEST The Manual Magnetic oi perf...

Страница 24: ...ch dia Heptane 10 3 30 Sunlight reflected modulated unmodulated 2 inch dia Heptane 10 3 30 70 w sodium vapor lamp unmodulated 5 1 5 2 inch dia Heptane 5 1 5 3 70 w sodium vapor lamp modulated 5 1 5 2 inch dia Heptane 5 1 5 3 250 w mercury vapor lamp unmodulated 5 1 5 2 inch dia Heptane 5 1 5 2 250 w mercury vapor lamp modulated 5 1 5 2 inch dia Heptane 5 1 5 3 300 w incandescent lamp unmodulated 5...

Страница 25: ...istance feet m Horizontal degrees Typical Horiz Response Time seconds Vertical degrees Typical Vert Response Time seconds Black Powder 40 Grams 5 1 5 45 45 0 04 0 03 45 30 0 04 0 04 FALSE ALARM IMMUNITY High Sensitivity TDSA On Quick Fire Off False Alarm Souce Distance feet m Modulated Response Unmodulated Response Sunlight direct reflected No alarm No alarm Vibration NA No alarm No alarm Arc weld...

Страница 26: ...s E F and G T5 Class I Division 2 Groups A B C and D T3 Class II Division 2 Groups F and G T3 Class III Enclosure Type 4X Infrared Flame Detector Controller X98AF series rated 18 30 Vdc 2 1 Watts to 16 5 Watts Relay contacts rated 5 Amps 30 Vdc Instructions AutroFlame X98AF 116 P X98AF IGB Rev D 2012 02 02 Autronica Fire and Security AS 95 8683 Rev 8 11 Page 26 ...

Страница 27: ...artment in type of explosion protection flameproof enclosure d or in type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The metal housing for the Infrared IR...

Страница 28: ...nts shall be certified to E generation or ATEX standards in type of explosion protection increased safety e or flameproof enclosure d as applicable suitable for the conditions of use and correctly installed They shall maintain the degree of ingress protection IP66 for the apparatus Unused apertures shall be closed with suitable blanking elements Note For ATEX installations the X98AF detector housi...

Страница 29: ... explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The metal housing for the Infrared IR flame detector type X98AF must be electrically connected to earth ground Fo...

Страница 30: ...Fire Detection and Fire Alarm Systems BASIS OF APPROVAL DIN EN 54 Part 10 05 02 Flame Detectors Instructions for the application of the approval component system The installation shall take into account that the orientation arrow on the flame detector is directed upwards as the view angle in this direction is 90 The IR flame detector corresponds to class 1 Instructions AutroFlame X98AF 116 P X98AF...

Отзывы: