Important
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
attEntIon
The X98AF includes the Automatic Optical
Integrity (
oi
®
) feature — a calibrated performance
test that is automatically performed once per
minute to verify complete detector operation
capabilities.
no testing with an external test
lamp is required.
DESCRIPTION
The evolution continues with the new X98AF IR
Flame Detector. The X98AF meets the most stringent
requirements worldwide with advanced detection
capabilities and immunity to extraneous sources,
combined with a superior mechanical design. The
detector is equipped with both automatic and manual
oi
test capability. The detector has Division and Zone
explosion-proof ratings and is suitable for use in indoor
and outdoor applications.
The standard output configuration includes fire, fault and
auxiliary relays. Output options include:
–
0 to 20 mA output (in addition to the three relays)
–
Pulse output for compatibility with existing controller
based systems (with fire and fault relays)
–
HART Communication
A tricolor LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
The X98AF housing is available in copper-free aluminum
or stainless steel, both with NEMA 4X and IP66 rating.
OuTpuTs
Relays
The standard detector is furnished with fire, fault and
auxiliary relays. All three relays are rated 5 amperes
at 30 Vdc.
The Fire Alarm relay has redundant terminals and
normally open / normally closed contacts, normally
de-energized operation, and latching or non-latching
operation.
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.