Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
39
3.4.1.3
CH3-S2UI-1
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
400101(0064)
03/06/16 R/W CH3 Input Set
Copy
CH3 copy input
parameter
Refer to channel
table.
※
4
-
None
400102(0065)
03/06/16 R/W CH3 Pen Record CH3 display and record
measuring value
0:OFF, 1:ON
-
ON
400103(0066)
03/06/16 R/W CH3 Pen Color CH3 record color
0:Violet, 1:Red,
2:Gray, 3:Green,
4:Blue, 5:Brown
-
Automati
c
set(CH1
to CH6)
(CH7 to
CH12)
Specify color.
400104(0067)
03/06/16 R/W CH3 Record
Zone
CH3 record zone
0:None, Zone1 to
Zone n
-
Zone(1
to N)
400105(0068)
03/06/16 R/W CH3 Tag Name CH3 channel name
1 to 6 characters
-
"CH-
□□"
400106(0069)
400107(006A)
400108(006B)
03/06/16 R/W CH3 Input Type CH3 input specification
Refer to input type
table.
※
5
-
TC-K
400109(006C)
03/06/16 R/W
CH3
Range/Scale
Point
CH3 decimal point
0:0, 1:0.0, 2:0.00,
3:0.000, 4:0.0000
-
Range
which
has
decimal
point
- TC/RTD type:
only available
0, 0.0
- Analog type:
Supports all. But
for Two Unit,
available 0:0,
1:0.0, 2:0.00
400110(006D)
03/06/16 R/W
CH3
Temp/Display
Unit
CH3 temperature unit
(300209) Refer to
address.
-
℃
- TC/RTD type:
0:
℃
, 1:
℉
, 2:
˚K
-Analog type:
Supports all.
400111(006E)
03/06/16 R/W
CH3 Low
Range/Low
Graph Scale
※
7
CH3 lower limit input
value/CH3 lower limit
graph scale value
Min. value of sensor
input range to upper
limit input value/ Upper
limit graph scale value
- F.S 5%
-
-200
Refer to range
decimal point set
table.
※
6
400112(006F)
03/06/16 R/W
CH3 High
Range/High
Graph Scale
※
7
CH3 upper limit input
value/CH3 higher limit
graph scale value
Lower limit input value/
lower limit graph scale
value + F.S 5%) to
Max. sensor input
range
-
1350.0
400113(0070)
03/06/16 R/W CH3 Low Scale CH3 analog lower limit
scale value
-99999 to 99999
Digit 0.0
Applied
depending on
the number of
decimal point of
CH3
Range/Scale
Point.
Ex) When scale
pointer value is
0.0, if inputting
9999, it is
recognized as
999.9
400114(0071)
400115(0072)
03/06/16 R/W CH3 High Scale CH3 analog upper limit
scale value
-99999 to 99999
Digit 100.0
400116(0073)
400117(0074)
03/06/16 R/W CH3 Special
Function
CH3 special function
TC/RTD input:0:None,
1:Difference
Analog input:0:Linear,
1:Root, 2:Square,
3:Two Unit
-
None
400118(0075)
03/06/16 R/W Two Unit
Two Unit conversion
value
1 to 35
Digit 3
If 100 is set, it is
recognized as
1.00.
400119(0076)
03/06/16 R/W CH3 Ref
Channel
CH3 reference channel
Refer to channel
table.
※
4
-
None
400120(0077)
03/06/16 R/W CH3 Input Bias CH3 error correction
-9999 to 9999
Digit 0000
Uses correction
value which
applies scale
decimal point.
400121(0078)
03/06/16 R/W CH3 Span
CH3 gradient adjustment 0.100 to 5.000
Multipl
e
1.000
If 1000 is set, it
is recognized as
Содержание krn100 series
Страница 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Страница 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Страница 82: ......