3 Modbus Mapping Table
28
© Copyright Reserved Autonics Co., Ltd.
3.2
Read Discrete Input Status(Func 02)
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
100001 (0000) 02
R
P.END
P.END(No recording
paper alarm) lamp
0:OFF, 1:ON
-
-
100002 (0001) 02
R
ALARM
ALARM output lamp
0:OFF, 1:ON
-
-
Marks ON when
even 1 alarm
turns ON.
100003 (0002) 02
R
ALARM -1
SLOT 7
S7AO-1 output
lamp
0:OFF, 1:ON
-
-
Alarm 1
100004 (0003) 02
R
ALARM -2
S7AO-2 output
lamp
0:OFF, 1:ON
-
-
Alarm 2
100005 (0004) 02
R
ALARM -3
S7AO-3 output
lamp
0:OFF, 1:ON
-
-
Alarm 3
100006 (0005) 02
R
ALARM -4
S7AO-4 output
lamp
0:OFF, 1:ON
-
-
Alarm 4
100007 (0006) 02
R
ALARM -5
S7AO-5 output
lamp
0:OFF, 1:ON
-
-
Alarm 5
100008 (0007) 02
R
ALARM -6
S7AO-6 output
lamp
0:OFF, 1:ON
-
-
Alarm 6
100009 (0008) 02
R
ALARM -7
SLOT 8
S8AO-1 output
lamp
0:OFF, 1:ON
-
-
Alarm 7
100010 (0009) 02
R
ALARM -8
S8AO-2 output
lamp
0:OFF, 1:ON
-
-
Alarm 8
100011 (000A) 02
R
ALARM -9
S8AO-3 output
lamp
0:OFF, 1:ON
-
-
Alarm 9
100012 (000B) 02
R
ALARM -10
S8AO-4 output
lamp
0:OFF, 1:ON
-
-
Alarm 10
100013 (000C) 02
R
ALARM -11
S8AO-5 output
lamp
0:OFF, 1:ON
-
-
Alarm 11
100014 (000D) 02
R
ALARM -12
S8AO-6 output
lamp
0:OFF, 1:ON
-
-
Alarm 12
100015 (000E) 02
R
ALARM -13
SLOT 9
S9AO-1 output
lamp
0:OFF, 1:ON
-
-
Alarm 13
100016 (000F) 02
R
ALARM -14
S9AO-2 output
lamp
0:OFF, 1:ON
-
-
Alarm 14
100017 (0010) 02
R
ALARM -15
S9AO-3 output
lamp
0:OFF, 1:ON
-
-
Alarm 15
100018 (0011) 02
R
ALARM -16
S9AO-4 output
lamp
0:OFF, 1:ON
-
-
Alarm 16
100019 (0012) 02
R
ALARM -17
S9AO-5 output
lamp
0:OFF, 1:ON
-
-
Alarm 17
100020 (0013) 02
R
ALARM -18
S9AO-6 output
lamp
0:OFF, 1:ON
-
-
Alarm 18
100021 (0014) 02
R
ALARM -19
SLOT 10
S10AO-1
output lamp
0:OFF, 1:ON
-
-
Alarm 19
100022 (0015) 02
R
ALARM -20
S10AO-2
output lamp
0:OFF, 1:ON
-
-
Alarm 20
100023 (0016) 02
R
ALARM -21
S10AO-3
output lamp
0:OFF, 1:ON
-
-
Alarm 21
100024 (0017) 02
R
ALARM -22
S10AO-4
output lamp
0:OFF, 1:ON
-
-
Alarm 22
100025 (0018) 02
R
ALARM -23
S10AO-5
output lamp
0:OFF, 1:ON
-
-
Alarm 23
100026 (0019) 02
R
ALARM -24
S10AO-6
output lamp
0:OFF, 1:ON
-
-
Alarm 24
100027 (001A) 02
R
DI
DI
input
lamp
0:OFF, 1:ON
-
-
Marks ON when
even 1 digital
input turns ON.
100028 (001B) 02
R
DI-1
SLOT 7
S7DI-1 input 0:OFF, 1:ON
Varies input
value from DI
status.
1. In case of
Level:
When DI input is
Short, it is 1.
When DI input is
Open, it is 0.
2. In case of
Edge:
When DI input
Digital Input1
100029 (001C) 02
R
DI-2
S7DI-2 input 0:OFF, 1:ON
Digital Input2
100030 (001D) 02
R
DI-3
S7DI-3 input 0:OFF, 1:ON
Digital Input3
100031 (001E) 02
R
DI-4
S7DI-4 input 0:OFF, 1:ON
Digital Input4
100032 (001F) 02
R
DI-5
S7DI-5 input 0:OFF, 1:ON
Digital Input5
100033 (0020) 02
R
DI-6
S7DI-6 input 0:OFF, 1:ON
Digital Input6
100034 (0021) 02
R
DI-7
SLOT 8
S8DI-1 input 0:OFF, 1:ON
Digital Input7
100035 (0022) 02
R
DI-8
S8DI-2 input 0:OFF, 1:ON
Digital Input8
100036 (0023) 02
R
DI-9
S8DI-3 input 0:OFF, 1:ON
Digital Input9
100037 (0024) 02
R
DI-10
S8DI-4 input 0:OFF, 1:ON
Digital Input10
100038 (0025) 02
R
DI-11
S8DI-5 input 0:OFF, 1:ON
Digital Input11
100039 (0026) 02
R
DI-12
S8DI-6 input 0:OFF, 1:ON
Digital Input12
Содержание krn100 series
Страница 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Страница 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Страница 82: ......