3
Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
37
3.4.1.2
CH2-S1UI-2
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
400051 (0032)
03/06/16 R/W CH2 Input Set
Copy
CH2 copy input
parameter
Refer to channel table.
※
4
-
None
400052 (0033)
03/06/16 R/W CH2 Pen Record CH2 display and record
measuring value
0:OFF, 1:ON
-
ON
400053 (0034)
03/06/16 R/W CH2 Pen Color CH2 record color
0:Violet, 1:Red, 2:Gray,
3:Green, 4:Blue, 5:Brown -
Automati
c
set(CH1
to CH6)
(CH7 to
CH12)
Specify color.
400054 (0035)
03/06/16 R/W CH2 Record
Zone
CH2 record zone
0:None, Zone1 to Zone n -
Zone(1
to N)
400055 (0036)
03/06/16 R/W CH2 Tag Name CH2 channel name
1 to 6 characters
-
"CH-
□□"
400056 (0037)
400057 (0038)
400058 (0039)
03/06/16 R/W CH2 Input Type CH2 input specification
Refer to input type
table.
※
5
-
TC-K
400059 (003A) 03/06/16 R/W
CH2
Range/Scale
Point
CH2 decimal point
0:0, 1:0.0, 2:0.00,
3:0.000, 4:0.0000
-
Range
which
has
decimal
point
- TC/RTD type:
only available
0, 0.0
- Analog type:
Supports all. But
for Two Unit,
available 0:0,
1:0.0, 2:0.00
400060 (003B) 03/06/16 R/W
CH2
Temp/Display
Unit
CH2 temperature unit
(300209) Refer to
address.
-
℃
- TC/RTD type:
0:
℃
, 1:
℉
, 2:
˚K
-Analog type:
Supports all.
400061 (003C) 03/06/16 R/W
CH2 Low
Range/Low
Graph Scale
※
7
CH2 lower limit input
value/CH2 lower limit
graph scale value
Min. value of sensor
input range to upper limit
input value/ Upper limit
graph scale value - F.S
5%
-
-200
Refer to range
decimal point set
table.
※
6
400062 (003D) 03/06/16 R/W
CH2 High
Range/High
Graph Scale
※
7
CH2 upper limit input
value/CH2 higher limit
graph scale value
Lower limit input value/
lower limit graph scale
value + F.S 5%) to Max.
sensor input range
-
1350.0
400063 (003E)
03/06/16 R/W CH2 Low Scale CH2 analog lower limit
scale value
-99999 to 99999
Digit 0.0
Applied
depending on
the number of
decimal point of
CH2
Range/Scale
Point.
Ex) When scale
pointer value is
0.0, if inputting
9999, it is
recognized as
999.9
400064 (003F)
400065 (0040)
03/06/16 R/W CH2 High Scale CH2 analog upper limit
scale value
-99999 to 99999
Digit 100.0
400066 (0041)
400067 (0042)
03/06/16 R/W CH2 Special
Function
CH2 special function
TC/RTD input:0:None,
1:Difference
Analog input:0:Linear,
1:Root, 2:Square, 3:Two
Unit
-
None
400068 (0043)
03/06/16 R/W Two Unit
Two Unit conversion
value
1 to 35
Digit 3
If 100 is set, it is
recognized as
1.00.
400069 (0044)
03/06/16 R/W CH2 Ref
Channel
CH2 reference channel Refer to channel table.
※
4
-
None
400070 (0045)
03/06/16 R/W CH2 Input Bias CH2 error correction
-9999 to 9999
Digit 0000
Uses correction
value which
applies scale
decimal point.
400071 (0046)
03/06/16 R/W CH2 Span
CH2 gradient adjustment 0.100 to 5.000
Multi
ple 1.000
If 1000 is set, it
is recognized as
Содержание krn100 series
Страница 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Страница 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Страница 82: ......