3 Modbus Mapping Table
64
© Copyright Reserved Autonics Co., Ltd.
3.4.2.5
CH5-S3AI-1
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
400801 (0320)
03/06/16 R/W Alarm Set Copy
Copy alarm parameter Refer to channel table.
※
8
-
None
CH-1 to CH-12
400802 (0321)
03/06/16 R/W Alarm1 Type
Alarm 1 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo,
5:SBA, 6:P.END
-
PV.Hi
400803 (0322)
03/06/16 R/W Alarm1 Ref CH
Alarm 1 reference
channel
Refer to channel table.
※
8
-
None
CH-1 to CH-12
400804 (0323)
03/06/16 R/W Alarm1 Option
Alarm 1 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400805 (0324)
03/06/16 R/W Alarm1 Value
Alarm 1 set value
F.S. by each channel
Digit 1350.0
400806 (0325)
400807 (0326)
03/06/16 R/W Alarm1 Hysteresis Alarm 1 hysteresis
001 to 999
Digit 001
400808 (0327)
03/06/16 R/W Alarm1 ON Delay Alarm 1 output ON
delay time
0 to 3600
Sec. 0
400809 (0328)
03/06/16 R/W Alarm1 OFF Delay Alarm 1 output OFF
delay time
0 to 3600
Sec. 0
400810 (0329)
03/06/16 R/W Alarm1 Alarm No Alarm 1 output alarm
number
Refer to channel table.
※
8
-
None
400811 (032A) 03/06/16 R/W Alarm2 Type
Alarm 2 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo,
5:SBA, 6:P.END
-
None
400812 (032B) 03/06/16 R/W Alarm2 Ref
Channel
Alarm 2 reference
channel
Refer to channel table.
※
8
-
None
400813 (032C) 03/06/16 R/W Alarm2 Option
Alarm 2 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400814 (032D) 03/06/16 R/W Alarm2 Value
Alarm 2 set value
F.S. by each channel
Digit 0
400815 (032E)
400816 (032F) 03/06/16 R/W Alarm2 Hysteresis Alarm 2 hysteresis
001 to 999
Digit 001
400817 (0330)
03/06/16 R/W Alarm2 ON Delay Alarm 2 output ON
delay time
0 to 3600
Sec. 0
400818 (0331)
03/06/16 R/W Alarm2 OFF Delay Alarm 2 output OFF
delay time
0 to 3600
Sec. 0
400819 (0332)
03/06/16 R/W Alarm2 Alarm No Alarm 2 output alarm
number
Refer to channel table.
※
8
-
None
400820 (0333)
03/06/16 R/W Alarm3 Type
Alarm 3 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo,
5:SBA, 6:P.END
-
OFF
400821 (0334)
03/06/16 R/W Alarm3 Ref
Channel
Alarm 3 reference
channel
Refer to channel table.
※
8
-
None
400822 (0335)
03/06/16 R/W Alarm3 Option
Alarm 3 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400823 (0336)
03/06/16 R/W Alarm3 Value
Alarm 3 set value
F.S. by each channel
Digit 0
400824 (0337)
400825 (0338)
03/06/16 R/W Alarm3 Hysteresis Alarm 3 hysteresis
001 to 999
Digit 001
400826 (0339)
03/06/16 R/W Alarm3 ON Delay Alarm 3 output ON
delay time
0 to 3600
Sec. 0
400827 (033A) 03/06/16 R/W Alarm3 OFF Delay Alarm 3 output OFF
delay time
0 to 3600
Sec. 0
400828 (033B) 03/06/16 R/W Alarm3 Alarm No Alarm 3 output alarm
number
Refer to channel table.
※
8
-
None
400829 (033C) 03/06/16 R/W Alarm4 Type
Alarm 4 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo,
5:SBA, 6:P.END
-
OFF
400830 (033D) 03/06/16 R/W Alarm4 Ref
Channel
Alarm 4 reference
channel
Refer to channel table.
※
8
-
None
400831 (033E) 03/06/16 R/W Alarm4 Option
Alarm 4 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400832 (033F) 03/06/16 R/W Alarm4 Value
Alarm 4 set value
F.S. by each channel
Digit 0
400833 (0340)
400834 (0341)
03/06/16 R/W Alarm4 Hysteresis Alarm 4 hysteresis
001 to 999
Digit 001
400835 (0342)
03/06/16 R/W Alarm4 ON Delay Alarm 4 output ON
delay time
0 to 3600
Sec. 0
400836 (0343)
03/06/16 R/W Alarm4 OFF Delay Alarm 4 output OFF
delay time
0 to 3600
Sec. 0
400837 (0344)
03/06/16 R/W Alarm4 Alarm No Alarm 4 output alarm
number
Refer to channel table.
※
8
-
None
400838 to
400850
03/06/16 R/W Reserved
Содержание krn100 series