3
Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
65
3.4.2.6
CH6-S3AI-2
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
400851 (0352)
03/06/16 R/W Alarm Set Copy
Copy alarm parameter Refer to channel table.
※
8
-
None
CH-1 to CH-12
400852 (0353)
03/06/16 R/W Alarm1 Type
Alarm 1 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
PV.Hi
400853 (0354)
03/06/16 R/W Alarm1 Ref CH
Alarm 1 reference
channel
Refer to channel table.
※
8
-
None
CH-1 to CH-12
400854 (0355)
03/06/16 R/W Alarm1 Option
Alarm 1 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400855 (0356)
03/06/16 R/W Alarm1 Value
Alarm 1 set value
F.S. by each channel
Digit 1350.0
400856 (0357)
400857 (0358)
03/06/16 R/W Alarm1 Hysteresis Alarm1 hysteresis
001 to 999
Digit 001
400858 (0359)
03/06/16 R/W Alarm1 ON Delay Alarm 1 output ON
delay time
0 to 3600
Sec. 0
400859 (035A) 03/06/16 R/W Alarm1 OFF Delay Alarm 1 output OFF
delay time
0 to 3600
Sec. 0
400860 (035B) 03/06/16 R/W Alarm1 Alarm No Alarm 1 output alarm
number
Refer to channel table.
※
8
-
None
400861 (035C) 03/06/16 R/W Alarm2 Type
Alarm 2 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
None
400862 (035D) 03/06/16 R/W Alarm2 Ref
Channel
Alarm 2 reference
channel
Refer to channel table.
※
8
-
None
400863 (035E) 03/06/16 R/W Alarm2 Option
Alarm 2 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400864 (035F) 03/06/16 R/W Alarm2 Value
Alarm 2 set value
F.S. by each channel
Digit 0
400865 (0360)
400866 (0361)
03/06/16 R/W Alarm2 Hysteresis Alarm 2 hysteresis
001 to 999
Digit 001
400867 (0362)
03/06/16 R/W Alarm2 ON Delay Alarm 2 output ON
delay time
0 to 3600
Sec. 0
400868 (0363)
03/06/16 R/W Alarm2 OFF Delay Alarm 2 output OFF
delay time
0 to 3600
Sec. 0
400869 (0364)
03/06/16 R/W Alarm2 Alarm No Alarm 2 output alarm
number
Refer to channel table.
※
8
-
None
400870 (0365)
03/06/16 R/W Alarm3 Type
Alarm 3 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
OFF
400871 (0366)
03/06/16 R/W Alarm3 Ref
Channel
Alarm 3 reference
channel
Refer to channel table.
※
8
-
None
400872 (0367)
03/06/16 R/W Alarm3 Option
Alarm 3 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400873 (0368)
03/06/16 R/W Alarm3 Value
Alarm 3 set value
F.S. by each channel
Digit 0
400874 (0369)
400875 (036A) 03/06/16 R/W Alarm3 Hysteresis Alarm 3 hysteresis
001 to 999
Digit 001
400876 (036B) 03/06/16 R/W Alarm3 ON Delay Alarm 3 output ON
delay time
0 to 3600
Sec. 0
400877 (036C) 03/06/16 R/W Alarm3 OFF Delay Alarm 3 output OFF
delay time
0 to 3600
Sec. 0
400878 (036D) 03/06/16 R/W Alarm3 Alarm No Alarm 3 output alarm
number
Refer to channel table.
※
8
-
None
400879 (036E) 03/06/16 R/W Alarm4 Type
Alarm 4 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
OFF
400880 (036F) 03/06/16 R/W Alarm4 Ref
Channel
Alarm 4 reference
channel
Refer to channel table.
※
8
-
None
400881 (0370)
03/06/16 R/W Alarm4 Option
Alarm 4 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400882 (0371)
03/06/16 R/W Alarm4 Value
Alarm 4 set value
F.S. by each channel
Digit 0
400883 (0372)
400884 (0373)
03/06/16 R/W Alarm4 Hysteresis Alarm 4 hysteresis
001 to 999
Digit 001
400885 (0374)
03/06/16 R/W Alarm4 ON Delay Alarm 4 output ON
delay time
0 to 3600
Sec. 0
400886 (0375)
03/06/16 R/W Alarm4 OFF Delay Alarm 4 output OFF
delay time
0 to 3600
Sec. 0
400887 (0376)
03/06/16 R/W Alarm4 Alarm No Alarm 4 output alarm
number
Refer to channel table.
※
8
-
None
400888 to
400900
03/06/16 R/W Reserved
Содержание krn100 series
Страница 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Страница 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Страница 82: ......