Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
51
3.4.1.9
CH9-S5UI-1
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
400401 (0190) 03/06/16 R/W CH9 Input Set
Copy
CH9 copy input
parameter
Refer to channel
table.
※
4
-
None
400402 (0191) 03/06/16 R/W CH9 Pen Record CH9 display and record
measuring value
0:OFF, 1:ON
-
ON
400403 (0192) 03/06/16 R/W CH9 Pen Color CH9 record color
0:Violet, 1:Red,
2:Gray, 3:Green,
4:Blue, 5:Brown
-
Automati
c
set(CH1
to CH6)
(CH7 to
CH12)
Specify color.
400404 (0193) 03/06/16 R/W CH9 Record
Zone
CH9 record zone
0:None, Zone1 to
Zone n
-
Zone(1
to N)
400405 (0194)
03/06/16 R/W CH9 Tag Name CH9 channel name
1 to 6 characters
-
"CH-
□□"
400406 (0195)
400407 (0196)
400408 (0197) 03/06/16 R/W CH9 Input Type CH9 input specification
Refer to input type
table.
※
5
-
TC-K
400409 (0198) 03/06/16 R/W
CH9
Range/Scale
Point
CH9 decimal point
0:0, 1:0.0, 2:0.00,
3:0.000, 4:0.0000
-
Range
which
has
decimal
point
- TC/RTD type:
only available
0, 0.0
- Analog type:
Supports all. But
for Two Unit,
available 0:0,
1:0.0, 2:0.00
400410 (0199) 03/06/16 R/W
CH9
Temp/Display
Unit
CH9 temperature unit
(30209) Refer to
address.
-
℃
- TC/RTD type:
0:
℃
, 1:
℉
, 2:
˚K
-Analog type:
Supports all.
400411 (019A) 03/06/16 R/W
CH9 Low
Range/Low
Graph Scale
※
7
CH9 lower limit input
value/CH9 lower limit
graph scale value
Min. value of sensor
input range to upper
limit input value/ Upper
limit graph scale value
- F.S 5%
-
-200
Refer to range
decimal point set
table.
※
6
400412 (019B) 03/06/16 R/W
CH9 High
Range/High
Graph Scale
※
7
CH9 upper limit input
value/CH9 higher limit
graph scale value
Lower limit input value/
lower limit graph scale
value + F.S 5%) to
Max. sensor input
range
-
1350.0
400413 (019C)
03/06/16 R/W CH9 Low Scale CH9 analog lower limit
scale value
-99999 to 99999
Digit 0.0
Applied
depending on
the number of
decimal point of
CH9
Range/Scale
Point.
Ex) When scale
pointer value is
0.0, if inputting
9999, it is
recognized as
999.9
400414 (019D)
400415 (019E)
03/06/16 R/W CH9 High Scale CH9 analog upper limit
scale value
-99999 to 99999
Digit 100.0
400416 (019F)
400417 (01A0) 03/06/16 R/W CH9 Special
Function
CH9 special function
TC/RTD
input :0:None,
1:Difference
Analog input:0:Linear,
1:Root, 2:Square,
3:Two Unit
-
None
400418 (01A1) 03/06/16 R/W Two Unit
Two Unit conversion
value
1 to 35
Digit 3
If 100 is set, it is
recognized as
1.00.
400419 (01A2) 03/06/16 R/W CH9 Ref
Channel
CH9 reference channel
Refer to channel
table.
※
4
-
None
400420 (01A3) 03/06/16 R/W CH9 Input Bias CH9 error correction
-9999 to 9999
Digit 0000
Uses correction
value which
applies scale
decimal point.
400421 (01A4) 03/06/16 R/W CH9 Span
CH9 gradient adjustment 0.100 to 5.000
Multipl 1.000
If 1000 is set, it
Содержание krn100 series
Страница 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Страница 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Страница 82: ......