3 Modbus Mapping Table
34
© Copyright Reserved Autonics Co., Ltd.
3.4
Read Holding Register(Func 03) / Preset Single
Register(Func 06) / Preset Multiple Registers(Func 16)
3.4.1
INPUT SETUP(Input setting)
3.4.1.1
CH1-S1UI-1
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
400001 (0000) 03/06/16 R/W CH1 Input Set
Copy
CH1 copy input
parameter
Refer to channel table.
※
4
-
None
400002 (0001) 03/06/16 R/W CH1 Pen Record CH1 display and record
measuring value
0:OFF, 1:ON
-
ON
400003 (0002) 03/06/16 R/W CH1 Pen Color CH1 record color
0:Violet, 1:Red, 2:Gray,
3:Green, 4:Blue,
5:Brown
-
Automati
c
set(CH1
to CH6)
(CH7 to
CH12)
Specify color.
400004 (0003) 03/06/16 R/W CH1 Record
Zone
CH1 record zone
0:None, Zone1 to Zone n -
Zone(1
to N)
400005 (0004)
03/06/16 R/W CH1 Tag Name CH1 channel name
1 to 6 characters
-
"CH-
□□"
400006 (0005)
400007 (0006)
400008 (0007) 03/06/16 R/W CH1 Input Type CH1 input specification
Refer to input type
table.
※
5
-
TC-K
400009 (0008) 03/06/16 R/W
CH1
Range/Scale
Point
CH1 decimal point
0:0, 1:0.0, 2:0.00,
3:0.000, 4:0.0000
-
Range
which
has
decimal
point
- TC/RTD type:
only available
0, 0.0
- Analog type:
Supports all. But
for Two Unit,
available 0:0,
1:0.0, 2:0.00
400010 (0009) 03/06/16 R/W
CH1
Temp/Display
Unit
CH1 temperature unit
(300209) Refer to
address.
-
℃
- TC/RTD type:
0:
℃
, 1:
℉
, 2:
˚K
-Analog type:
Supports all.
400011 (000A) 03/06/16 R/W
CH1 Low
Range/Low
Graph Scale
※
7
CH1 lower limit input
value/CH1 lower limit
graph scale value
Min. value of sensor
input range to upper limit
input value/ Upper limit
graph scale value - F.S
5%
-
-200
Refer to range
decimal point set
table.
※
6
400012 (000B) 03/06/16 R/W
CH1 High
Range/High
Graph Scale
※
7
CH1 upper limit input
value/CH1 higher limit
graph scale value
Lower limit input value/
lower limit graph scale
value + F.S 5%) to Max.
sensor input range
-
1350.0
400013 (000C) 03/06/16 R/W CH1 Low Scale CH1 analog lower limit
scale value
-99999 to 99999
Digit 0.0
Applied
depending on
the number of
decimal point of
CH1
Range/Scale
Point.
Ex) When scale
pointer value is
0.0, if inputting
9999, it is
recognized as
999.9.
400014 (000D)
400015 (000E)
03/06/16 R/W CH1 High Scale CH1 analog upper limit
scale value
-99999 to 99999
Digit 100.0
400016 (000F)
400017 (0010) 03/06/16 R/W CH1 Special
Function
CH1 special function
TC/RTD input:0:None,
1:Difference
Analog input:0:Linear,
1:Root, 2:Square, 3:Two
Unit
-
None
400018 (0011) 03/06/16 R/W Two Unit
Two Unit conversion
value
1 to 35
Digit 3
If 100 is set, it is
recognized as
1.00.
Содержание krn100 series
Страница 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Страница 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Страница 82: ......