Installation and
Safety Guidelines
Installing the DeviceNet
Slave Module
2–2
Installing the D0–DEVNETS Slave Module
D0–DEVNETS DeviceNet Slave
Module User Manual, Rev A
Installing the D0–DEVNETS Slave Module
The DIP switch, SW1 must be set before installing the DeviceNet slave module in the
DL05 option slot or in one of the DL06 option slots. The following diagram shows the
location of the DIP switch.
Note:
Be sure to look closely at the default settings below. If you are connecting to
an existing DeviceNet network, you may need to change the DeviceNet Baud Rate
on your D0–DEVNETS.
The factory default baud rate is 125kbps.
SW2 SW3
Node Address
1
2
3
4
5
6
O
F
F
SW1
DIP Switch
SW1
1
2
5
6
4
3
DeviceNet Baud Rate
Slave I/O Only Mode
Adapter Diagnostic Information
Hold Outputs (on Comm. Error)
Parameter Initializing
OFF
Set SW1–1 and SW1–2 for the DeviceNet baud rate.
DeviceNet Baud Rate
Baud Rate
SW1–1
SW1–2
125 kbps
OFF
OFF
250 kbps
ON
OFF
500 kbps
OFF
ON
Reserved
ON
ON
Setting the DIP
Switch (SW1)
Содержание D0-DEVNETS
Страница 1: ...D0 DEVNETS DeviceNet Slave Module User Manual Manual Number D0 DEVNETS M...
Страница 24: ...1A Specifications In This Appendix Specifications...
Страница 27: ...1B Tables In This Appendix DeviceNet Tables...
Страница 34: ...1C Image Table Mapping In This Appendix Image Table Mapping...
Страница 44: ...1E D0 DEVNETS Think Do Entivity Setup In This Appendix D0 DEVNETS Think Do Entivity Setup...
Страница 52: ...1F OIT with D0 DEVNETS In This Appendix OIT with D0 DEVNETS and Think Do Entivity...
Страница 61: ...1 G D0 DEVNETS and Allen Bradley Set up In This Appendix Setup D0 DEVNETS with Allen Bradley RSNetworxt...