Installing the DeviceNet
Slave Module
Installation and
Safety Guidelines
2–9
Installing the D0–DEVNETS Slave Module
D0–DEVNETS DeviceNet Slave
Module User Manual, Rev A
D0–DEVNETS Parameter Setup
The DL05/06 PLCs reserve several V–memory locations for storing the DEVNETS
parameters. These special registers store the I/O ranges. The parameters are
stored in the DL05/06 systems FLASH memory, and are not lost when the PLC is
powered off.
System
V-memory
Description of Contents
Factory Default Value
Range
V7610
Input starting address
V40400
V40400 – 40417 (X0–377)
V40500 – 40517 (Y0–377)
V40600 – 40637 (C0–777)
V41000 – 41017 (S0 – 377)
V41100 – 41107 (T0 – 177)
V41140 – 41147 (CT0 – 177)
V41200 – 41237 (SP0 – 777)
V7611
Input number of bytes
2 Bytes
0 – 8 Bytes
V7612
Output starting address
V40500
V40400 – 40417 (X0 – 377)
V40500 – 40517 (Y0–377)
V40600 – 40637 (C0–777)
V41000 – 41017 (S0–377)
V41100 – 41107 (T0 – 177)
V41140 – 41147 (CT0 – 177)
V41200 – 41237 (SP0 – 777)
V7613
Output number of bytes
2 Bytes
0 – 8 Bytes
V7614
Input starting V–memory location
V3000
V0 – 7777
V7615
Input V–memory number of bytes
58 Bytes
0 – 128 Bytes
V7616
Output starting V–memory location
V3100
V0 – 7377
V7617
Output V–memory number of bytes
52 Bytes
0 – 128 Bytes
D0–DEVNETS
Default Parameters
Содержание D0-DEVNETS
Страница 1: ...D0 DEVNETS DeviceNet Slave Module User Manual Manual Number D0 DEVNETS M...
Страница 24: ...1A Specifications In This Appendix Specifications...
Страница 27: ...1B Tables In This Appendix DeviceNet Tables...
Страница 34: ...1C Image Table Mapping In This Appendix Image Table Mapping...
Страница 44: ...1E D0 DEVNETS Think Do Entivity Setup In This Appendix D0 DEVNETS Think Do Entivity Setup...
Страница 52: ...1F OIT with D0 DEVNETS In This Appendix OIT with D0 DEVNETS and Think Do Entivity...
Страница 61: ...1 G D0 DEVNETS and Allen Bradley Set up In This Appendix Setup D0 DEVNETS with Allen Bradley RSNetworxt...