Appendix C Error Codes
Appendix E
Think & Do Setup
Think & Do Setup
E–4
D0–DEVNETS DeviceNet Slave
Module User Manual, Rev A
For those who are using a DL05 with D0–DEVNETS as a PLC, for local I/O control,
on a DeviceNet network with Think & Do Studio, the following example shows how to
setup the DL05 and the adapter for use as a PLC on the network.
Use the following steps to setup the adapter with the DL05 PLC for local control on a
network. The RLL program is edited using
Direct
SOFT32 programming software.
Set DIP switch, SW1, as follows:
1. SW1–1: OFF
SW1–2: ON (communications rate 500K or the baud rate of your choice)
SW1–3: OFF
SW1–4: OFF
SW1–5: OFF
SW1–6: ON (initial value)
SW1–6 sets up the following system parameter defaults:
V7610 = O40400 / V7611 = 2
V7612 = O40500 / V7613 = 2
V7614 = O3000 / V7615 = 128
V7616 = O3100 / V7617 = 128
2. Set rotary switch, SW2 = 02, SW3 = 0.
3. Add the following RLL code to the DL05 program:
SP0
LD
OUT
V7611
K4
Load the total number of scan cycles.
V40401 = X20–X37
LD
OUT
V40401
V7765
Set to read 4 bytes to display active input points.
SP1
4. Return the DL05 to RUN mode.
Setup Think & Do
with DL05 on a
network
Содержание D0-DEVNETS
Страница 1: ...D0 DEVNETS DeviceNet Slave Module User Manual Manual Number D0 DEVNETS M...
Страница 24: ...1A Specifications In This Appendix Specifications...
Страница 27: ...1B Tables In This Appendix DeviceNet Tables...
Страница 34: ...1C Image Table Mapping In This Appendix Image Table Mapping...
Страница 44: ...1E D0 DEVNETS Think Do Entivity Setup In This Appendix D0 DEVNETS Think Do Entivity Setup...
Страница 52: ...1F OIT with D0 DEVNETS In This Appendix OIT with D0 DEVNETS and Think Do Entivity...
Страница 61: ...1 G D0 DEVNETS and Allen Bradley Set up In This Appendix Setup D0 DEVNETS with Allen Bradley RSNetworxt...